Plan Review Notes For Permit 15020647 |
Permit Number |
15020647 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-03-23 16:05:04 | 3/23/2015 | | PROJECT: SUSHIYAMA SIGN | | PERMIT#: 15020647 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | ELECTRICAL PLAN REVIEW | | ACTION: APPROVED WITH EXCEPTION | | | | 1) ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING | | ? FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND | | INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS | | OTHERWISE APPROVED BY SPECIAL PERMISSION. 600.3 | | LISTING. | | | | 2) EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER | | CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE | | LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY | | OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL | | UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC | | 600.6(A)(1) | | | | 3) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 | | SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT | | OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & | | TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME | | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING | | DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E | | 505.2.4 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|