Plan Review Notes
Plan Review Notes For Permit 15020549
Permit Number 15020549
Review Stop E
Sequence Number 2
Notes
Date Text
2015-06-25 15:33:006/25/2015
 PROJECT: SPRINGDALE
 PERMIT#: 15020549
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) NEC 215.2 MINIMUM RATING AND SIZE.
 PROVIDE A LOAD CALCULATION IN ACCORDANCE WITH THE
 PROVISIONS OF THE THE NEC 220.16. 215.2 MINIMUM RATING
 AND SIZE AND REVISE THE RISER DIAGRAM AS NEEDED .
 (A) FEEDERS NOT MORE THAN 600 VOLTS. (1) GENERAL.
 FEEDER CONDUCTORS SHALL HAVE AN AMPACITY NOT LESS THAN
 REQUIRED TO SUPPLY THE LOAD AS CALCULATED IN PARTS III,
 IV, AND V OF ARTICLE 220.
  
 2) REVISE THE RISER DIAGRAM. THE CURRENT DESIGN IS
 INDICATING FEEDER CONDUCTORS UTILIZING A SERVICE
 DISCONNECT AS A RACEWAY.
 2A) REVISE THE GROUNDING ELECTRODE SYSTEM IN THE RISER
 DIAGRAM. THE CURRENT DESIGN INDICATES THE GROUNDING
 ELECTRODE CONDUTOR TERMINATING AT ONLY ONE OF THE TWO
 MAIN DISCONNECTS.
  
 3) NEC 110.33(B)
 PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO
 GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL
 EQUIPMENT INSTALLED IN THE ATTIC FOR THE AHU(S). NEC
 110.33(B)
  
 4) FBC-E 402.4.5 RECESSED LIGHTING.
 RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED
 LUMINAIRES SHALL BE IC-RATED AND LABELED AS MEETING
 ASTM E 283 WHEN TESTED AT 1.57 PSF (75 PA) PRESSURE
 DIFFERENTIAL WITH NO MORE THAN 2.0 CFM (0.944 L/S) OF
 AIR MOVEMENT FROM THE CONDITIONED SPACE TO THE CEILING
 CAVITY. ALL RECESSED LUMINAIRES SHALL BE SEALED WITH A
 GASKET OR CAULK BETWEEN THE HOUSING AND THE INTERIOR
 WALL OR CEILING COVERING.
  
 5) FBC-E 404.1 LIGHTING EQUIPMENT.
 A MINIMUM OF 50 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICENCY
 LAMPS.
  
 6) NEC210.8
 CLARIFY ALL OUTLTS REQUIRING GFI PROTECTION. SEVERAL
 LOCATIONS NOT INDICATING PROPER GFI PROTECTION. GARAGE
 DOOR OUTLETS , KITCHEN COUNTER OUTLETS, BACK LANIA
 OUTLETS. SEE NEC210.8
  
 7) NEC 210.12, 406.11
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SWIMMING POOLS, GENERATORS. LOW
 VOLTAGE SYSTEMS, SECURITY, CABLE TV,, CCTV,
 AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  
  