Plan Review Notes For Permit 15020549 |
Permit Number |
15020549 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-03-27 13:34:05 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | COMMENTS. | | CODE: 2010 FBC | | | | 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS BASED | | ON THE BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION | | OF THE HOUSE AS REQUIRED BY SEC. 403.6 OF 2010 | | FBC-ENERGY CONSERVATION. INFORMATION SUBMITTED IS ONLY | | A SUMMARY. | | | | 2- ENERGY CALCULATIONS NEED TO BE REVISED BECAUSE IT | | DOESN'T MATCH INFORMATION SHOWN ON ARCHITECTURAL PLANS. | | FOR EXAMPLE ARCHITECT DIDN'T DESIGNED THE HOUSE WITH AN | | UNVENTED ATTIC. IT LOOKS LIKE EQUIPMENT SIZING | | CALCULATIONS WERE DONE BASED ON THE INFORMATION SHOWN | | ON THE ENERGY CALCULATIONS. INFORMATION ON THE | | EQUIPMENT SIZING CALCULATIONS NEED TO MATCH | | ARCHITECTURAL PLANS INCLUDING THE WALL FINISHES, ETC. | | THERE IS NOT SIDING FINISH ON WALLS. REVISE ALL THE | | INFORMATION AS REQUIRED TO MATCH ARCHITECTURAL PLANS. | | SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. | | | | 3-PROVIDE MANUFACTURER SPECS FOR THE OUTDOOR KITCHEN | | HOOD AS REQUIRED D BY SEC. M1302.1 OF 2010 | | FBC-RESIDENTIAL. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|