2015-03-27 13:34:05NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS BASED
 ON THE BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION
 OF THE HOUSE AS REQUIRED BY SEC. 403.6 OF 2010
 FBC-ENERGY CONSERVATION. INFORMATION SUBMITTED IS ONLY
 A SUMMARY.
  
 2- ENERGY CALCULATIONS NEED TO BE REVISED BECAUSE IT
 DOESN'T MATCH INFORMATION SHOWN ON ARCHITECTURAL PLANS.
 FOR EXAMPLE ARCHITECT DIDN'T DESIGNED THE HOUSE WITH AN
 UNVENTED ATTIC. IT LOOKS LIKE EQUIPMENT SIZING
 CALCULATIONS WERE DONE BASED ON THE INFORMATION SHOWN
 ON THE ENERGY CALCULATIONS. INFORMATION ON THE
 EQUIPMENT SIZING CALCULATIONS NEED TO MATCH
 ARCHITECTURAL PLANS INCLUDING THE WALL FINISHES, ETC.
 THERE IS NOT SIDING FINISH ON WALLS. REVISE ALL THE
 INFORMATION AS REQUIRED TO MATCH ARCHITECTURAL PLANS.
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 3-PROVIDE MANUFACTURER SPECS FOR THE OUTDOOR KITCHEN
 HOOD AS REQUIRED D BY SEC. M1302.1 OF 2010
 FBC-RESIDENTIAL.
  