Date Text
2015-03-28 14:27:023/28/2015
 PROJECT: SPRINGDALE
 PERMIT#: 15020549
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) NEC 215.2 MINIMUM RATING AND SIZE.
 PROVIDE A LOAD CALCULATION IN ACCORDANCE WITH THE
 PROVISIONS OF THE THE NEC 220.16. 215.2 MINIMUM RATING
 AND SIZE AND REVISE THE RISER DIAGRAM AS NEEDED .
 (A) FEEDERS NOT MORE THAN 600 VOLTS. (1) GENERAL.
 FEEDER CONDUCTORS SHALL HAVE AN AMPACITY NOT LESS THAN
 REQUIRED TO SUPPLY THE LOAD AS CALCULATED IN PARTS III,
 IV, AND V OF ARTICLE 220.
  
 2) NEC 440.11
 REVISE THE SYMBOL SHOWN FOR THE AHU 1 IN THE ATTIC
 SPACE IN THE GARAGE AND FOR THE CU UNIT(S) OUTSIDE. THE
 SYMBOL INDICATES A 240V RECEPTACLE OUTLET WHERE AN A/C
 UNITS REQUIRE DISCONNECTING MEANS CAPABLE OF
 DISCONNECTING THE UNITS FROM THE CIRCUIT CONDUCTORS.
 NEC 440.11
  
 3) NEC 110.33(B)
 PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO
 GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL
 EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR
 MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES.
 NEC 110.33(B)
  
 4) FBC-E 402.4.5 RECESSED LIGHTING.
 RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED
 LUMINAIRES SHALL BE IC-RATED AND LABELED AS MEETING
 ASTM E 283 WHEN TESTED AT 1.57 PSF (75 PA) PRESSURE
 DIFFERENTIAL WITH NO MORE THAN 2.0 CFM (0.944 L/S) OF
 AIR MOVEMENT FROM THE CONDITIONED SPACE TO THE CEILING
 CAVITY. ALL RECESSED LUMINAIRES SHALL BE SEALED WITH A
 GASKET OR CAULK BETWEEN THE HOUSING AND THE INTERIOR
 WALL OR CEILING COVERING.
  
 5) FBC-E 404.1 LIGHTING EQUIPMENT.
 A MINIMUM OF 50 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS.
  
 6) FBC-R 315.1 CARBON MONOXIDE PROTECTION.
 PROVIDE CARBON MONOXIDE DETECTOS WITHIN 10FT. OF
 SLEEPING AREAS.
  
 7) NEC210.8
 CLARIFY ALL OUTLTS REQUIRING GFI PROTECTION. SEVERAL
 LOCATIONS NOT INDICATING PROPER GFI PROTECTION. SEE
 NEC210.8
  
 8) NEC 210.12, 406.11
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SWIMMING POOLS, GENERATORS. LOW
 VOLTAGE SYSTEMS, SECURITY, CABLE TV,, CCTV,
 AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  
  