2015-03-28 14:27:02 | 3/28/2015 |
| PROJECT: SPRINGDALE |
| PERMIT#: 15020549 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) NEC 215.2 MINIMUM RATING AND SIZE. |
| PROVIDE A LOAD CALCULATION IN ACCORDANCE WITH THE |
| PROVISIONS OF THE THE NEC 220.16. 215.2 MINIMUM RATING |
| AND SIZE AND REVISE THE RISER DIAGRAM AS NEEDED . |
| (A) FEEDERS NOT MORE THAN 600 VOLTS. (1) GENERAL. |
| FEEDER CONDUCTORS SHALL HAVE AN AMPACITY NOT LESS THAN |
| REQUIRED TO SUPPLY THE LOAD AS CALCULATED IN PARTS III, |
| IV, AND V OF ARTICLE 220. |
| |
| 2) NEC 440.11 |
| REVISE THE SYMBOL SHOWN FOR THE AHU 1 IN THE ATTIC |
| SPACE IN THE GARAGE AND FOR THE CU UNIT(S) OUTSIDE. THE |
| SYMBOL INDICATES A 240V RECEPTACLE OUTLET WHERE AN A/C |
| UNITS REQUIRE DISCONNECTING MEANS CAPABLE OF |
| DISCONNECTING THE UNITS FROM THE CIRCUIT CONDUCTORS. |
| NEC 440.11 |
| |
| 3) NEC 110.33(B) |
| PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO |
| GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL |
| EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR |
| MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES. |
| NEC 110.33(B) |
| |
| 4) FBC-E 402.4.5 RECESSED LIGHTING. |
| RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL |
| ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED |
| LUMINAIRES SHALL BE IC-RATED AND LABELED AS MEETING |
| ASTM E 283 WHEN TESTED AT 1.57 PSF (75 PA) PRESSURE |
| DIFFERENTIAL WITH NO MORE THAN 2.0 CFM (0.944 L/S) OF |
| AIR MOVEMENT FROM THE CONDITIONED SPACE TO THE CEILING |
| CAVITY. ALL RECESSED LUMINAIRES SHALL BE SEALED WITH A |
| GASKET OR CAULK BETWEEN THE HOUSING AND THE INTERIOR |
| WALL OR CEILING COVERING. |
| |
| 5) FBC-E 404.1 LIGHTING EQUIPMENT. |
| A MINIMUM OF 50 PERCENT OF THE LAMPS IN PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY |
| LAMPS. |
| |
| 6) FBC-R 315.1 CARBON MONOXIDE PROTECTION. |
| PROVIDE CARBON MONOXIDE DETECTOS WITHIN 10FT. OF |
| SLEEPING AREAS. |
| |
| 7) NEC210.8 |
| CLARIFY ALL OUTLTS REQUIRING GFI PROTECTION. SEVERAL |
| LOCATIONS NOT INDICATING PROPER GFI PROTECTION. SEE |
| NEC210.8 |
| |
| 8) NEC 210.12, 406.11 |
| ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| |
| SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| ARE REQUIRED FOR SWIMMING POOLS, GENERATORS. LOW |
| VOLTAGE SYSTEMS, SECURITY, CABLE TV,, CCTV, |
| AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |