Plan Review Notes
Plan Review Notes For Permit 15020549
Permit Number 15020549
Review Stop B
Sequence Number 1
Notes
Date Text
2015-03-24 11:36:32NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FORR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 2- SHEET G-1:
 A) REVISE LOAD SCHEDULE LIVE LOAD ON THE ROOFF BOTTOM
 CHORD TO COMPLY WITH FOOTNOTES B AND G OF TABLE R301.5
 OF 2010 FBC-RESIDENTIAL. AND, COORDINATE INFORMATION
 WITH THE DESIGN LOADS SHOWN ON SHEET S1.00.
  
 B) REVISE LOAD SCHEDULE INFORMATION. ACCORDING TO SEC.
 R301.2.1.4 OF 2010 FBC-RESIDENTIAL THIS BUILDING IS
 LOCATED IN EXPOSURE "C" NOT "B". REVISE AS REQUIRED.
  
 3- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF 2010
 FBC-RESIDENTIAL.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR , MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND THE DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS TO FBC. VALUATION WAS UPDATED TO $485,032.
 THE PERMIT FEE BALANCE IS $8652.02.
  
 5- SHEET A-1:
 A) SPECIFY THE ATTIC ACCESS SIZE FOR THE ATTIC ACCESS
 SHOWN IN MASTER BEDROOM CLOSET. SEC. 807 OF 2010
 FBC-RESIDENTIAL.
  
 B) PROVIDE SPECIFICATIONS FOR THE GARAGE DOOR LEADING
 TO THE INTERIOR OF THE HOUSE TO SHOW COMPLIANCE WITH
 SEC. R302.5.1 OF 2010 FBC-RESIDENTIAL.
  
 6- TYPICAL WALL SECTION ON SHEET A-2:
 A) DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS.
  
 B) WALL SECTION CALLS FOR 2" CONT. SOFFIT VENTING,
 WHILE GENERAL NOTES ON SAME DRAWINGS STATES "NUMBER OF
 OF ROOF VENTS TO BE DETERMINED BY BUILDER". IT'S NOT
 THE BUILDER RESPONSIBILITY TO DETERMINE THE NUMBER OF
 VENTS. IT'S THE DESIGNER OF RECORD RESPONSIBILITY.
 REVISE AS REQUIRED. SEC. R806 OF 2010 FBC-RESIDENTIAL.
  
 C) SPECIFY FOOTING MINIMUM DEPTH AS REQUIRED BY SEC.
 R403.1.4 OF 2010 FBC-RESIDENTIAL. COORDINATE WITH
 STRUCTURAL DRAWINGS.
  
 D) THE CEILING INSULATION R- VALUE IS NOT TO BE
 VERIFIED BY THE BUILDER. IT'S THE DESIGNER OF RECORD
 RESPONSIBILITY TO SPECIFY IT. ON THE OTHER HAND
 COORDINATE WITH THE ENERGY CALCULATIONS. INFORMATION
 DOESN'T'T MATCH. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. ARCHITECTURAL PLANS AND ENERGY
 CALCULATIONS NEED TO BE COORDINATED.
  
 E) OVERHANG AT GARAGE WINDOWS DETAIL. PROVIDE COMPLETE
 SPECIFICATIONS. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SEC. R301.1. PROVIDE COMPLETE
 SPECIFICATIONS FOR THE LATH AND STUCCO SOFFIT SHOWING
 COMPLIANCE WITH SEC. R703.1.3 OF 2010 FBC-RESIDENTIAL.
  
 F) FRONT ELEVATION: CLARIFY WHAT'S " CONCRETE FLAT TILE
 W/ FLAT STUCCO SOFFIT, TYP." SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 7- SHEET S1.00:
 A) SPECIFY ALL LIVE AND DEAD LOADS. NOTE #7 OF
 PREFABRICATED WOOD TRUSSES ONLY SPECIFY THE DEAD LOADS.
 CLEARLY SPECIFY ALL LIVE AND DEAD LOADS, INCLUDING THE
 ATTIC LIVE LOADS AS REQUIRED BY FOOT NOTES B AND G OF
 TABLE R301.5 OF 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE DOOR AND WINDOW STRUCTURAL BUCK DETAIL
 SHOWING COMPLIANCE WITH SEC. R612.10.2.1 OF 2010
 FBC-RESIDENTIAL. (NOTE: DETAIL 2/S1.00 STATES "AS PER
 DOOR MANUFACTURER PRODUCT APPROVAL". DESIGNER OF RECORD
 NEED TO SPECIFY THE BUCK SIZE AND ATTACHMENT).
  
 8- SOIL TEST REPORT: SOIL TEST REPORT SUBMITTED IS
 MISSING INFORMATION. PROVIDE ALL ALL THE INFORMATION
 REQUIRED BY SEC. 1803.6 OF 2010 FBC.
  
 9- ENERGY CALCULATIONS:
 A) REVISE INFORMATION ON CEILING TYPES ITEM #10.
 INFORMATION DOESN''T MATCH FLOOR PLANS. COORDINATE AS
 REQUIRED TO MATCH. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 B) REVISE DOOR INFORMATION ON PAGE 3 OF 6 TO-MATCH
 FLOOR PLANS AND PRODUCT APPROVALS SUBMITTED. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. (CLEARLY
 IDENTIFY ON-PLANS WHICH ARE THE INSULATED AND WOOD
 DOORS).
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) CONCRETE TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL
 FL14317-R4 SUBMITTED: THE MAXIMUM DESIGN PRESSURES FOR
 THIS UNDERLAYMENT IS -45PSF. SEE SEC. 5.5.2.1. THIS
 UNDERLAYMENT DOESN'T MEET THE DESIGN PRESSURES REQUIRED
 BY SEC. R301.1 OF 2010 FBC-RESIDENTIAL. PROVIDE PRODUCT
 APPROVAL THAT MEETS THE DESIGN PRESSURES FO ALL ROOF
 ZONES.
  
 B) CONCRETE ROOF TILE ADHESIVE IF SPECIFIED BY THE
 DESIGNER OF RECORD. SEE ITEM #6(A) ABOVE. NOTE: SEE
 ROOF TILE PRODUCT APPROVAL FOR LISTED ADHESIVES.
  
 C) BAHAMA SHUTTERS FLORIDA PRODUCT APPROVAL FL6566-R3:
 PROVIDE LEGIBLE DRAWINGS. SEC. 107.2.1.4 CITY
 AMENDMENTS TO FBC. LETTERING ON DRAWING SUBMITTED ARE
 TOO SMALL AND ARE NOT LEGIBLE. PLEASE PROVIDE LARGER
 PRINTS OR PRINT DRAWING IN A "LANDSCAPE" WAY. THAT WAY
 DRAWINGS WILL BE LEGIBLE.
  
 D) 8'-0" WIDE OVERHEAD GARAGE DOORS AS SHOWN ON PLANS.
 INFORMATION SUBMITTED IS FOR 16'-0" WIDE DOORS.
  
 E) FIXED WINDOW SIZES AS SHOWN ON PLANS IN THE MORNING
 AREA.
  
 F) ENTRY DOOR AS SHOWN ON PLANS.
  
 G) CEMENTIOUS SOFFIT AS SPECIFIED ON PLANS. SEE SEC.
 R616 OF 2020 FBC-RESIDENTIAL.
  
 H) PRECAST LINTELS AS SPECIFIED ON PLANS. (NOTE:
 DESIGNER OF RECORD MAY LIST THE MIAMI-DADE NOA OR
 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE SPECIFIED
 LINTEL).
  
 I) HUC410 CONNECTOR SHOWN ON THE TRUSS CONNECTOR
 SCHEDULE AND ALL THE CONNECTORS SPECIFIED ON FRAMING
 PLANS AND DETAILS THAT ARE NOT LISTED IN THE TRUSS
 CONNECTOR SCHEDULE. (NOTE: DESIGNER OF RECORD MAY LIST
 THE MIAMI-DADE NOA OR FLORIDA PRODUCT APPROVAL NUMBER
 NEXT TO THE SPECIFIED CONNECTOR ON EACH DETAIL).
  
 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN-WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 12- PROVIDE BAHAMA SHUTTERS COMPLETE INSTALLATION
 SCHEDULE (INCLUDING THE FAUX SHUTTERS SHOWN ON FRONT
 ELEVATION). SEE INSTALLATION SCHEDULE CITY SAMPLE OR
 PROVIDE ALL THE REQUIRED INFORMATION IN ANY-OTHER
 FORMAT. SEC. 107.2.1 CITY AMENDMENTS.
  
 13- TRUSS PACKAGE:
 A) COMPLETE TRUSS PACKAGE NEEDS TO BE REVIEWED AND
 APPROVED BY THE DESIGN PROFESSIONAL OF RECORD PRIOR TO
 SUBMITTAL.
  
 B) ALL ENGINEERED BEAMS AND TRUSS SHEETS NEED TO BE
 SIGNED AND SEALED AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE.
  
 NOTE: AFTER ABOVE CORRECTIONS ARE DONE, THEN THE TRUSS
 PACKAGE MAY BE SUBMITTED TO THE INSPECTOR AT TIME OF
 FRAMING INSPECTION INSTEAD RE-SUBMITTING THE TRUSS
 PACKAGE TO THIS OFFICE NOW. (FOR RESIDENTIAL PROJECTS
 ONLY).
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS AND AVOID
 CONFLICTS OR DELAYS.
 **** PLEASE REMOVE AND REPLACE ANY REVISE
 DRAWING/PRODUCT APRPOVAL TO EXPEDITE THE REVIEW
 PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712