2015-06-23 11:06:37705 NORTH OLIVE AVENUE
 TRACKING #15060302
 MASTER #14030096
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION ADDRESSING REVIEW
 COMMENTS*****
  
 GENERAL: COULD NOT LOCATE ANY VISIBLE SIGNALS WITHIN
 THE DWELLING UNITS. VISIBLE SIGNALS SHALL BE INSTALLED
 IN UNITS DESIGNED FOR THE HEARING IMPAIRED.
  
 GENERAL: EXPLAIN WHY THERE ARE MANUAL PULL STATIONS
 THROUGHOUT THE1ST FLOOR BUT NOT ON ANY OTHER LEVEL.
  
 GENERAL: VOICE EVACUATION - PROVIDE A PRE-RECORDED FIRE
 ALARM EVACUATION MESSAGE NOTIFYING OCCUPANTS AN
 EMERGENCY HAS BEEN REPORTED IN THE BUILDING, LOCATE THE
 NEAREST EXIT, AND EXIT THE BUILDING IMMEDIATELY. DO NOT
 USE THE ELEVATOR.
  
 GENERAL: PROVIDE FIRE INSPECTOR WITH A COPY OF THE
 RECORD OF COMPLETION DOCUMENTS PER NFPA 72.
  
 SHEET FA-101: PARKING GARAGE SEVERELY LACKING VISUAL
 NOTIFICATION DEVICES; TYPICAL ALL LEVELS. PROVIDE
 ADEQUATE NOTIFICATION PER NFPA 72.
  
 SHEET FA-102: NO NOTIFICATION APPLIANCE PROVIDED IN
 TRASH ROOM ADJACENT TO STAIR #3.
  
 SHEET FA-102: THERE APPEARS TO BE 6 TOILET ROOMS IN THE
 FITNESS AREA THAT HAVE FULL HEIGHT WALLS AND NO
 NOTIFICATION APPLIANCES WITHIN EACH UNIT.
  
 SHEET FA-102: MAIL ROOM APPEARS TO HAVE A FULL HEIGHT
 WALL OBSTRUCTING THE APPLIANCE STROBE.
  
 SHEET FA-103: NO NOTIFICATION APPLIANCE PROVIDED IN
 STORAGE ROOM #248.
  
 SHEET FA-104: AMENITIES AREA IS UTILIZING CEILING
 MOUNTED NOTIFICATION DEVICES. THIS AREA IS SURROUNDED
 BY GLAZING (VAST AMOUNTS OF NATURAL LIGHTING) THAT MAY
 REQUIRE ADDITIONAL VISUAL NOTIFICATION DEVICE TO COMPLY
 WITH NFPA 72.
  
 SHEET FA-104: NO NOTIFICATION APPLIANCE PROVIDED IN
 STORAGE ROOM #245.
  
 SHEET FA-104: NO NOTIFICATION APPLIANCE PROVIDED IN
 STORAGE ROOMS #242 AND #243; TYPICAL ALL LEVELS ABOVE.
  
 SHEET FA-117: SMOKE DETECTORS SHALL NOT BE INSTALLED IN
 UNSPRINKLERED ELEVATOR HOISTWAYS UNLESS THEY ARE
 INSTALLED TO ACTIVATE THE ELEVATOR HOISTWAY SMOKE
 RELIEF EQUIPMENT (NFPA 72 SECTION 21.3.6).
  
 SHEET FA-118: SMOKE DETECTORS SHALL NOT BE INSTALLED IN
 UNSPRINKLERED ELEVATOR HOISTWAYS UNLESS THEY ARE
 INSTALLED TO ACTIVATE THE ELEVATOR HOISTWAY SMOKE
 RELIEF EQUIPMENT (NFPA 72 SECTION 21.3.6).
  
 CENTRAL STATION SERVICE: THE PRIME CONTRACTOR SHALL
 CONSPICUOUSLY INDICATE THAT THE FIRE ALARM SYSTEM
 PROVIDING SERVICE AT A PROTECTED PREMISES COMPLIES WITH
 ALL THE REQUIREMENTS OF THIS CODE THROUGH THE USE OF A
 SYSTEMATIC FOLLOW-UP PROGRAM UNDER THE CONTROL OF THE
 ORGANIZATION THAT HAS LISTED THE PRIME CONTRACTOR.
 DOCUMENTATION INDICATING CODE COMPLIANCE OF THE
 FIRE ALARM SYSTEM SHALL BE ISSUED BY THE ORGANIZATION
 THAT HAS LISTED THE PRIME CONTRACTOR. THE DOCUMENTATION
 SHALL INCLUDE, AT A MINIMUM, THE FOLLOWING INFORMATION:
 (1) NAME OF THE PRIME CONTRACTOR INVOLVED WITH THE
 ONGOING CODE COMPLIANCE OF THE CENTRAL STATION SERVICE
 (2) FULL DESCRIPTION OF THE FIRE ALARM SYSTEM AS
 INSTALLED (3) ISSUE AND EXPIRATION DATES OF THE
 DOCUMENTATION
 (4) NAME, ADDRESS, AND CONTACT INFORMATION OF THE
 ORGANIZATION ISSUING THE DOCUMENT
 (5) IDENTIFICATION OF THE AUTHORITY(IES) HAVING
 JURISDICTION FOR THE CENTRAL STATION SERVICE
 INSTALLATION
 THE DOCUMENTATION SHALL BE PHYSICALLY POSTED WITHIN 3
 FEET OF THE FIRE ALARM CONTROL UNIT, AND COPIES OF THE
 DOCUMENTATION SHALL BE MADE AVAILABLE TO THE AHJ.
  
 NOTE: FIRE ALARM ACCEPTANCE TESTING WILL REQUIRE
 24-HOURS ON STANDBY FOLLOWED BY 5-MINUTES OF ALARM AND
 15-MINUTES OF ALARM FOR THE VOICE EVACUATION SYSTEM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
 CONTRACTOR'S FIRE ALARM DRAWINGS ARE AWAITING REVIEW
 UNTIL THE ENGINEER OF RECORD REVISES THE CONSTRUCTION
 DRAWINGS AND INDICATES THE CHANGES MADE FROM THE
 ORIGINAL DESIGN. THE EOR DRAWINGS (REVISED PERMIT
 #15060302) WERE SUBMITTED, REVIEWED AND FAILED ON
 06/11/15 DUE TO THE COMMENTS SHOWN BELOW:
  
 NO ADDRESS INDICATED ON THE PLANS OR IN THE TITLEBLOCK.
  
 NO REVISION CLOUDS, DELTAS OR DETAILED SUMMARY PROVIDED
 INDICATED WHAT HAS CHANGED ON THE PLANS.
  
 PLANS WERE ORIGINALLY SUBMITTED DIGITALLY; REVISION WAS
 SUBMITTED AS HARD COPY. PLEASE RESUBMIT THE REVISED
 PLANS DIGITALLY.
  
  