2015-03-03 09:13:44 | BUILDING PLAN REVIEW |
| MASTER: 14040379 |
| PERMIT: 15020521 |
| ADD: 2101 OKEECHOBEE BLVD |
| CONT: FLORES CONSTRUCTION |
| TEL: (813) 323-7895 |
| E-MAIL:[email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| ELECTRONICALLY |
| UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| SUBMISSION OPTIONS ARE AS FOLLOWS: |
| 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| NAMING CONVENTION FOR EACH DOCUMENT |
| 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| AVAILABLE |
| |
| 1ST REVIEW |
| DATE: MARCH 03/ 2015 |
| ACTION: DENIED |
| |
| 1) A LETTER FROM THE QUALIFIER OF BOTH THE PRIME/ |
| MASTER CONTRACTOR (HEDRICK BROTHERS) AND MEZZANINE |
| CONTRACTOR MUST BE PROVIDED BEFORE THE MEZZINE PERMIT |
| CAN BE ISSUED, IF THE MEZZANINE CONTRACTOR WISHES TO |
| START WORK BEFORE THE SHELL / MASTER/ PRIME PERMIT WORK |
| HAS RECEIVED A CERTIFICATE OFOCCUPANCY, AGREEING THEY |
| WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER. |
| PLEASE PROVIDE THE PERMIT NUMBER, ADDRESS WITH SUITE |
| NUMBER WITHIN THE DOCUMENT. |
| |
| 2) THE SUBMITTED MEZININE PLANS WERE NOT REVIEWED BY |
| THE DESIGNER OF RECORD. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| |
| 3A) THE MEZZININE PLANS DO NOT SHOW ANY GUARD RAIL |
| SYSTEM AROUND THE OPEN AREA AT THE PART DELIVERY AREA |
| OR THE VLM. 2010 FBC-B 1013.1 WHERE REQUIRED. |
| GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING |
| SURFACES, INCLUDING MEZZANINES, EQUIPMENT PLATFORMS, |
| STAIRS, RAMPS AND LANDINGS THAT ARE LOCATED MORE THAN |
| 30 INCHES (762 MM) MEASURED VERTICALLY TO THE FLOOR. |
| |
| 3B) SHOW COMPLIANCE WITH; 1013.3 OPENING LIMITATIONS. |
| EXCEPTIONS: 4. IN AREAS THAT ARE NOT OPEN TO THE PUBLIC |
| WITHIN OCCUPANCIES IN GROUP I-3, F, H OR S, AND FOR |
| ALTERNATING TREAD DEVICES AND SHIP LADDERS, GUARDS |
| SHALL NOT HAVE OPENINGS WHICH ALLOW PASSAGE OF A SPHERE |
| 21 INCHES (533 MM) IN DIAMETER. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |