 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE REVISED PLAN SHOWS 4 SETS OF 4, 500 MCM WITH A
 #2 EQUIPMENT GROUND. RISER DIAGRAM. REVISE TO INDICATE
 ONE SET AND INDICATE THE CONDUCTOR TYPE.
  
 2) INDICATE THE LOCATION OF THE EXISTING 200AMP PANEL,
 THE NEW GUTTER AND NEW 200AMP PANEL ADDED IN SUITE #20.
  
 3) CREATE A NEW SHEET THAT SHOWS THE REVIESD RISER
 DIAGRAM AND THE REVISED DEMO INCLUDING THE PANEL
 LOCATIONS IN SUITE #20
  