Plan Review Notes For Permit 15020485 |
Permit Number |
15020485 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-03-16 08:24:07 | 3/16/2015 | | PROJECT: 5335 MILITARY TR | | PERMIT#: 14060910, REVISION TRACKING #15020485 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 2ND ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) THE REVISED PLAN SHOWS 4 SETS OF 4, 500 MCM WITH A | | #2 EQUIPMENT GROUND. RISER DIAGRAM. REVISE TO INDICATE | | ONE SET AND INDICATE THE CONDUCTOR TYPE. | | | | 2) INDICATE THE LOCATION OF THE EXISTING 200AMP PANEL, | | THE NEW GUTTER AND NEW 200AMP PANEL ADDED IN SUITE #20. | | | | 3) CREATE A NEW SHEET THAT SHOWS THE REVIESD RISER | | DIAGRAM AND THE REVISED DEMO INCLUDING THE PANEL | | LOCATIONS IN SUITE #20 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|