Plan Review Notes
Plan Review Notes For Permit 15020485
Permit Number 15020485
Review Stop E
Sequence Number 1
Notes
Date Text
2015-02-24 17:20:072/24/2015
 PROJECT: 5335 MILITARY TR
 PERMIT#: 14060910, REVISION TRACKING #15020485
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE THE RISER DIAGRAM TO ADDRESS THE RIVISION 5
 CLOUDED AREA FEEDING THE 400AMP METER FOR BAY 20.
  
 2) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 3) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16.
  
 4)PROVIDE A LOAD CALCULATION TO SHOW CAPACITY ON THE
 EXISTING SERVICE MAIN IS ADAQUATE TO SUPPORT THE
 ADDITIONAL LOAD. LOADS FOR NEW CIRCUITS OR EXTENDED
 CIRCUITS IN PREVIOUSLY WIRED DWELLING UNITS SHALL BE
 CALCULATED IN ACCORDANCE WITH EITHER 220.12 OR 220.14,
 AS APPLICABLE. NEC 220.16(2)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  