Plan Review Notes
Plan Review Notes For Permit 15020451
Permit Number 15020451
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-02-13 11:05:07THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 ON SHEET FA -1 THERE IS NO HORN STROBE LOCATED WITHIN
 THE AREA OF THE 1ST FLOOR HALLWAY/CLASSROOMS AREA.
 UNKNOWN IF THIS OMITTED BY ERROR.
  
 PLEASE CONDSIDER THE FOLLOWING AS PROVISO:
  
 THIS AREA DEVICE WILL BE COMFIRMED AND VERIFIED FOR
 AUDIBLE AND VISUAL NOTIFICATION ON FIRE INSPECTION.
 PROVIDE REVISION OR AS-BUILTS AS APPROPRIATE.