2015-02-19 07:37:51 | BUILDING PLAN REVIEW |
| PERMIT : 15020438 |
| EXPIRED:13050172 |
| ADD: 3001 TUXEDO AVE. |
| CONT: OLIVERI BROTHERS |
| TEL: (561) 478-7233 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| IMPORTANT NOTICE: EFFECTIVE MARCH 2, 2015 |
| ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| ELECTRONICALLY |
| UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| SUBMISSION OPTIONS ARE AS FOLLOWS: |
| 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL |
| SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| NAMING CONVENTION FOR EACH DOCUMENT |
| 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| AVAILABLE |
| |
| |
| 1ST REVIEW |
| DATE: THURS. FEB. 19/ 2015 |
| ACTION: DENIED |
| |
| 1) THE ORIGINAL EXPIRED PERMIT # 13050172 FOR TRUSS |
| REPAIR DOES NOT HAVE THE STRUCTURAL SHEETS S-1/ S-2 |
| SHEETS INCLUDED IN THIS PERMIT PACKAGE. IT APPEARS THAT |
| THE CONTRACTOR IS TRYING TO DO A RENEWAL PERMIT AS WELL |
| AS ADDITIONAL WORK NOT COVERED UNDER THE ORIGINAL SCOPE |
| OF THE PERMIT. THE PERMIT PLANS UNDER THE PERMIT |
| 13050172 WILL NEED TO BE SUBMITTED FOR THE RESTAMP OF |
| PLANS TO THE NEW PERMIT TRACKING NUMBER. A SECOND SET |
| WILL ALSO BE REQUIRED FOR THE RECORD RETENSION FOR THE |
| CITY. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2 CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL... |
| |
| 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| OTHER ITEMS RELATED TO RECORDS MANAGEMENT. |
| |
| NEW WORK SHOWN ON THE OLIVERI MILLWORK PLANS. |
| 2) SHEET A1.0 THE EAST ELEVATION SHOWS A SECTION LINE D |
| THROUGH THE BUILDING WHERE A NEW WALL IS TO BE BUILT TO |
| THE ROOF LINE. THIS LINE IS NOT SHOWN ON THE FLOOR |
| PLAN. THE FLOOR PLANS DO SHOW A BLUE LINE BEING BUILT |
| ON TOP OF AN EXISTING ROOM, IS THIS TO BE A |
| CONTINUATION OF THE EXISTING MEZZANINE? |
| IF SO, PLEASE PROVIDE THE LIFE SAFETY PLAN FOR THE |
| MEZZANINE WITH THE FOLLOWING INFORMATION: |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| 2.1) OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED. |
| 2.2) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| (SEE TABLE 503). |
| 2.3) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANCY LOAD |
| GROSS |
| NET |
| MEANS OF EGRESS |
| EXIT ACCESS |
| EXIT |
| EXIT DISCHARGE |
| STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| DOORS |
| EMERGENCY LIGHTING AND EXIT SIGNS |
| 2.4) STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| DESIGN LOADS- FOR MEZZANINE FLOOR LOADS |
| STRUCTURAL CALCULATIONS IF MEZZANINE IS FOR STORAGE |
| 125/ 250 LBS |
| WALLS SUPPORTING A MEZZANINE FLOOR LOAD |
| 2,5) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| FOLLOWING: |
| ACCESSIBLE ROUTE/ VERTICAL ACCESSIBILITY |
| 2.6) PROVIDE COMPLIANCE WITH 2010 FBC-B 505.2 AREA |
| LIMITATION FOR MEZZANINES. |
| 2.7) PROVIDE COMPLIANCE WITH 505.3 EGRESS |
| 2.8) OPENNESS 505.4. |
| |
| 3) THE NEW OR MOVED MACHINERY WILL NEED TO SHOW |
| COMPLIANCE WITH : |
| 3A) 2010 FBC-B [F] 510.2.1 LUMBER YARDS AND WOODWORKING |
| FACILITIES. |
| EQUIPMENT OR MACHINERY LOCATED INSIDE BUILDINGS AT |
| LUMBER YARDS AND WOODWORKING FACILITIES WHICH GENERATES |
| OR EMITS COMBUSTIBLE DUST SHALL BE PROVIDED WITH AN |
| APPROVED DUST-COLLECTION AND EXHAUST SYSTEM INSTALLED |
| IN CONFORMANCE WITH THIS SECTION AND THE FLORIDA FIRE |
| PREVENTION CODE. EQUIPMENT AND SYSTEMS THAT ARE USED TO |
| COLLECT, PROCESS OR CONVEY COMBUSTIBLE DUSTS SHALL BE |
| PROVIDED WITH AN APPROVED EXPLOSION-CONTROL |
| SYSTEM. |
| |
| 3B) 2010 FBC-B 511.1 DUST, STOCK AND REFUSE CONVEYING |
| SYSTEMS. |
| DUST, STOCK AND REFUSE CONVEYING SYSTEMS SHALL COMPLY |
| WITH THE PROVISIONS OF SECTION 510 AND SECTIONS 511.1.1 |
| THROUGH 511.2. UNLESS OTHERWISE SPECIFIED IN THIS |
| SECTION, DUST, STOCK AND REFUSE CONVEYING SYSTEMS SHALL |
| ALSO COMPLY WITH SECTION 510 AND NFPA 91. |
| |
| 3C) 2010 FBC-B F] 903.2.4.1 WOODWORKING OPERATIONS. AN |
| AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT |
| ALL GROUP F-1 OCCUPANCY FIRE AREAS THAT CONTAIN |
| WOODWORKING OPERATIONS IN EXCESS OF 2,500 SQUARE FEET |
| (232 M2) IN AREA WHICH GENERATE FINELY DIVIDED |
| COMBUSTIBLE WASTE OR USE FINELY DIVIDED COMBUSTIBLE |
| MATERIALS. |
| |
| 4) THERE IS A TECHNICAL SHEET MARKED AS EQUIPMENT # 27 |
| PLEASE PROVIDE THIS SHEET IN ENGLISH. 107.2.1.4 QUALITY |
| OF BUILDING PLANS. THE BUILDING OFFICIAL MAY ESTABLISH |
| THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS |
| AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO |
| ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE |
| SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, |
| OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT. |
| ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE |
| REQUIREMENTS OF FLORIDA STATUTES. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |