Plan Review Notes
Plan Review Notes For Permit 15020415
Permit Number 15020415
Review Stop B
Sequence Number 2
Notes
Date Text
2015-02-19 15:25:31PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO (2) SETS OF THE PRODUCT APPROVALS AS
 REQUIRED BY FBC 107.3.4.
  
 2) THE SYSTEM (W-61) THAT WAS SELECTED FROM THE
 CERTAINTEED MODIFIED ROOF SYSTEM PRODUCT APPROVAL
 (FL2533-R12) HAS A MAXIMUM DESIGN PRESSURE OF -52.5
 PSF. SUBMIT TWO SETS OF SIGNED AND SEALED ENHANCED
 FASTENING CALCULATIONS FROM A QUALIFIED DESIGN
 PROFESSIONAL FOR ROOF ZONES 2 AND 3. SEE NOTE #8 ON
 PAGE 2 OF 55. FBC-R 301.1
  
 3) NOA NO. 13-0419.04 THAT WAS SUBMITTED FOR THE
 ASPHALT ROOF SHINGLES HAS BEEN SUPERSEDED. SUBMIT TWO
 COPIES OF THE CURRENT NOA (NOA NO.14-1022.20). DCA RULE
 9N-3
  
  