Plan Review Notes For Permit 15020415 |
Permit Number |
15020415 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-02-19 15:25:31 | PLAN REVIEW COMMENTS | | | | 2ND REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT TWO (2) SETS OF THE PRODUCT APPROVALS AS | | REQUIRED BY FBC 107.3.4. | | | | 2) THE SYSTEM (W-61) THAT WAS SELECTED FROM THE | | CERTAINTEED MODIFIED ROOF SYSTEM PRODUCT APPROVAL | | (FL2533-R12) HAS A MAXIMUM DESIGN PRESSURE OF -52.5 | | PSF. SUBMIT TWO SETS OF SIGNED AND SEALED ENHANCED | | FASTENING CALCULATIONS FROM A QUALIFIED DESIGN | | PROFESSIONAL FOR ROOF ZONES 2 AND 3. SEE NOTE #8 ON | | PAGE 2 OF 55. FBC-R 301.1 | | | | 3) NOA NO. 13-0419.04 THAT WAS SUBMITTED FOR THE | | ASPHALT ROOF SHINGLES HAS BEEN SUPERSEDED. SUBMIT TWO | | COPIES OF THE CURRENT NOA (NOA NO.14-1022.20). DCA RULE | | 9N-3 | | | | |
|