2015-02-12 12:41:47PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOA NO. 10-1230.02 THAT WAS SUBMITTED FOR THE FLAT
 ROOF HAS BEEN SUPERSEDED. SUBMIT THE CURRENT NOA. DCA
 RULE 9N-3
  
 2) THE SYSTEM SELECTED ON PAGE 23 OF NOA NO. 10-1230.02
 HAS A MAXIMUM DESIGN PRESSURE OF -45 PSF AND LIMITATION
 #9, WHICH DOES NOT ALLOW IT TO BE INCREASED BY RATIONAL
 ANALYSIS. THE PERIMETER AND CORNER AREAS OF THE ROOF
 REQUIRE A LARGER UPLIFT PRESSURE. FBC 301.2.1
  
 3) NOA NO. 13- 0419.04 THAT WAS SUBMITTED FOR THE
 ASPHALT ROOF SHINGLES HAS BEEN SUPERSEDED. SUBMIT THE
 CURRENT NOA. DCA RULE 9N-3
  
 4) THE CALCULATED VALUE FOR THIS PROJECT IS $4,010.00
 BASED ON THE INFORMATION THAT WAS PROVIDED. IF YOU WISH
 TO DISPUTE THE VALUE, YOU WILL NEED TO SUBMIT A SIGNED
 COPY OF THE PROPOSAL/CONTRACT.
  
  