2015-02-28 08:58:201) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS &
 INSTASLLATION MANUALS FOR ALL GAS EQUIPMENT. EQUIPMENT
 SHALL BE LISTED AND LABELED PER THE 2010 FUEL GAS CODE
 SEC. 301.3, 2010 FBCR SEC.G2404.3.
 2) SHT. P-2 SHOWS PE GAS PIPE INSTALLED WITHIN THE
 STRUCTURE. PLASTIC PIPE SHALL BE INSTALLED OUTDOORS
 UNDERGROUND ONLY.PLASTIC PIPE SHALL NOT BE USED WITHIN
 OR UNDER ANY BUILDING OR SLAB PER THE 2010 FGC
 SEC.404.15.1.
  