Plan Review Notes For Permit 15020329 |
Permit Number |
15020329 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-02-12 09:03:30 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE. FBC | | 107.2.1 | | | | 2) THE POLYGLASS MODIFIED BITUMEN SYSTEM W-9 THAT WAS | | SELECTED HAS A MAXIMUM DESIGN PRESSURE OF - 90.0 PSF. | | THE PROJECT IS LOCATED IN EXPOSURE CATEGORY C, THE | | UPLIFT PRESSURE IN THE CORNER AREAS WILL EXCEED - 90.0 | | PSF. FBC R301.2.1 | | | | 3) SPECIFY THE SYSTEM AND THE MAXIMUM DESIGN PRESSURE | | FOR THE TILE ROOF UNDERLAYMENT THAT WILL BE USED. SEE | | PAGES 5 THROUGH 11 OF THE PRODUCT APPROVAL (FL529-R20) | | FBC R301.1 | | | | 4) SPECIFY THE TYPE AND PROFILE (LOW, MEDIUM OR HIGH) | | OF THE ENTEGRA ROOF TILE THAT WILL BE INSTALLED. FBC | | R301.1 | | | | 5) SPECIFY THE PADDY PLACEMENT AND ALLOWABLE | | OVERTURNING MOMENT FROM THE TABLE ON PAGE 3 OF PRODUCT | | APPROVAL FL6332-R4 FOR THE 3M AH-160 FOAM ROOF TILE | | ADHESIVE. | | |
|