Plan Review Notes
Plan Review Notes For Permit 15020304
Permit Number 15020304
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-02-13 13:45:33THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 ON SHEET CVR, AN INCORRECT REFENCE TO THE APPLICABLE
 NFPA 101 LIFE SAFETY CODE IS REFERENCED. THE CURRENT
 EDITION IS 2012, AND IS INCLUDED IN THE 5TH EDITION OF
 FLORIDA FIRE PREVENTION CODE. IT DOES NOT TO APPEAR TO
 HAVE NEGATIVELY IMPACTED YOUR SUBMITTAL. PLEASE MAKE
 THE CORRECTION ON ANY FUTURE SUBMITTALS.
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  