2015-02-26 07:39:28 | 2/25/2015 |
| PROJECT: LUX AUTO SPA SIGN |
| PERMIT#: 15020239 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE ELECTRICAL PLANS AND PERMIT INDICATE |
| COMPLIANCE WITH THE NEC ARTICLE 600 AND THE FBC CHAPTER |
| 5 SECTION 505.2.4. SEE BELOW: |
| |
| 2) ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING |
| ? FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND |
| INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS |
| OTHERWISE APPROVED BY SPECIAL PERMISSION. 600.3 |
| LISTING. |
| |
| 3) EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER |
| CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE |
| LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY |
| OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL |
| UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC |
| 600.6(A)(1) |
| |
| 4) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 |
| SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT |
| OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & |
| TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME |
| SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING |
| DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E |
| 505.2.4 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |