Plan Review Notes For Permit 15020238 |
Permit Number |
15020238 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-02-12 06:04:39 | 1) THERE IS AN UNVENTED SINK SHOWN ON THE PLUMBING | | RISER IN THE GARAGE BUT THE SINK IS NOT SHOWN ON THE | | FLOOR PLAN. CLARIFY. FIXTURES SHALL BE VENTED PER THE | | 2010 FBCR SEC.P3101.2 & P3101.2.1. | | 2) THE LAYOUT OF THE FIXTURES ON THE RISER DIAGRAM DOES | | NOT CORRELATE WITH THE FLOOR PLAN. WPB AMEND. TO 2010 | | FBC SEC. 107.2.1. | | 3) SIZE ALL THE VENTS ON THE PLUMBING RISER. WPB AMEND. | | TO 2010 FBCR 107.2.1. | | 4) THE WASHING MACHINE IS NOT VENTED. 2010 FBCR | | SEC.P3101.2 & P3101.2.1. | | 5) THERE IS AN UNVENTED SINK SHOWN ON THE RISER FOR THE | | GARAGE BUT THE SINK IS NOT SHOWN ON THE FLOOR PLAN. | | CLARIFY. | | 6) THERE IS A TUB AND WATER CLOSET SHOWN ON THE SECOND | | FLOOR OF THE MAIN HOUSE MASTER BATH BUT NOT SHOWN ON | | THE RISER. CLARIFY. | | 7) THE LAVATORY & SINK ON THE 2ND FLOOR GARAGE RISER | | CANNOT CONNECT TO THE SAME FIXTURE DRAIN.COMPLY WITH | | 2010 FBCR SEC.P3201.6. EACH FIXTURE SHALL CONNECT | | SEPARATELY TO THE STACK. | | 8) THE SECOND FLOOR BATH CNNOT DISCHARGE INTO THE SOIL | | STACK AS DESIGNED. 2010 FBCR SEC.P3108.4. | | 9) SHOW THE DIMENSIONS OF ALL SHOWERS (LXW). SHOWERS | | SHALL COMPLY WITH 2010 FBCR SEC. P 2708.1. SHOWERS | | SHALL HAVE A MINIMUM CLEAR AND UNOBSTRUCTED FINISHED | | WIDTH OF 22 INCHES PER 2010 FBCR SEC.P2708.1.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|