Plan Review Notes
Plan Review Notes For Permit 15020214
Permit Number 15020214
Review Stop G
Sequence Number 2
Notes
Date Text
2015-03-10 09:27:481) THE TYPE OF PIPE TO BE USED FOR THE GAS LINE IS
 SHOWN AS 3/4" TYPE L COPPER. SECTION G2414.5.2 OF THE
 2010 FBCR PROHIBITS THE USE OF COPPER IF THE GAS
 CONTAINS MORE THAN AN AVERAGE OF 0.3 GRAINS OF HYDROGEN
 SULFIDE PER 100 STANDARD CUBIC FEET OF GAS.
 VERIFICATION FROM THE GAS PURVEYOR SHALL BE SUBMITTED
 AS TO THE AMOUNT OF HYDROGEN SULFIDE CONTAINED IN THE
 GAS PER 100 CU. FT.
  