Plan Review Notes For Permit 15020214 |
Permit Number |
15020214 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-03-10 09:27:48 | 1) THE TYPE OF PIPE TO BE USED FOR THE GAS LINE IS | | SHOWN AS 3/4" TYPE L COPPER. SECTION G2414.5.2 OF THE | | 2010 FBCR PROHIBITS THE USE OF COPPER IF THE GAS | | CONTAINS MORE THAN AN AVERAGE OF 0.3 GRAINS OF HYDROGEN | | SULFIDE PER 100 STANDARD CUBIC FEET OF GAS. | | VERIFICATION FROM THE GAS PURVEYOR SHALL BE SUBMITTED | | AS TO THE AMOUNT OF HYDROGEN SULFIDE CONTAINED IN THE | | GAS PER 100 CU. FT. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|