Plan Review Notes
Plan Review Notes For Permit 15020214
Permit Number 15020214
Review Stop G
Sequence Number 1
Notes
Date Text
2015-02-07 09:51:321) INDICATE THE TYPE OF PIPE BEING INSTALLED. 2010 FBCR
 SEC.G2414.1.
 2) SHOW THE PIPE SIZES FOR THE GAS AND THE WATER
 LINES.2010FBCR SEC.G2413.1
 3) INDICATE THE PSI OF THE GAS SYSTEM.2010FBCR
 SEC.G2413.6.
 4) INDICATE THE TYPE OF GAS ON THE PLAN. (LP OR
 NATURAL),
 5) SHOW THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM.2010 FBCR G2412.8, G2413.2,
 6) SHOW THE DISTANCE FROM THE POINT OF DELIVERY TO THE
 MOST REMOTE OUTLET IN THE STRUCTURE. 2010 FBCR
 SEC.G2413.4.1.
 7) THERE IS A NOTE ON THE PLAN WITH AN ARROW POINTING
 TO THE HEATER WHICH IS ILLEGIBLE. CLARIFY.
 8) SHOW THE REQUIRED SHUTOFF VALVE ON THE GAS LINE.
 2010 FBCR SEC.G2420.1.
  