Plan Review Notes For Permit 15020200 |
Permit Number |
15020200 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-02-09 06:51:35 | 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE | | PURA SPRAY TAN BOOTHS. WPB AMEND. TO 2010 FBC | | SEC.107.2.1. | | 2) INDICATE THE TYPE OF EFFLUENT THAT WILL BE | | DISCHARGED TO THE SANITARY SYSTEM. WPB AMEND. TO 2010 | | FBC SEC.107.2.1. | | 3) RESEARCH ON THIS BOOTH SHOWS THE USE OF A FOUR PART | | SOLUTION. SUBMIT SPECIFICATIONS / MSDS FOR THE | | SOLUTIONS THAT WILL BE USED IN THE SPRAY TANNING | | PROCESS THE WATER SUPPLY TO THESE BOOTHS SHALL BE | | PROTECTED WITH A BACKFLOW PREVENTION DEVICE. 2010 FPC | | SEC.608.1. | | 4) SUBMIT 2 COPIES OF MANUF. SPECIFICATION SHEETS FOR | | THE LINT TRAP.WPB AMEND. TO 2010 FBC SEC.107.2.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|