Plan Review Notes For Permit 15020197 |
Permit Number |
15020197 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-02-24 17:38:50 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE TWO SETS OF | | DOOR SUBMITTALS. | | | | 2) THE DESIGN PRESSURES ON THE COVER SHEET (+ 50.5 / | | -50.5 PSF ) AND THE INSTALLATION DRAWINGS (+ 45.0 / - | | 40 PSF ) DO NOT MATCH. THE - 40 PSF IS NOT ADEQUATE FOR | | THIS TWO STORY STRUCTURE LOCATED IN EXPOSURE C. | | | | |
|