Plan Review Notes
Plan Review Notes For Permit 15020147
Permit Number 15020147
Review Stop B
Sequence Number 3
Notes
Date Text
2015-06-03 09:36:30RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- ENERGY CALCULATIONS SUBMITTED (SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION).
 A) FORM 402-2010 CAN NOT BE USED IF THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SEE GENERAL INSTRUCTIONS NOTE #1
 ON TOP OF FORM SUBMITTED.
  
 B) COMPLETE ALL THE INFORMATION ON TABLE 402A ON PAGE 2
 OF FORM SUBMITTED. THE INSTALLED VALUES MUST MEET OR
 EXCEED THE PERFORMANCE CRITERIA. AND, REVISE ALL THE
 INFORMATION ON PAGE ONE OF FORM SUBMITTED. SEE GENERAL
 INSTRUCTION #2 ON TOP OF FORM SUBMITTED.
  
 C) REVISE ITEM #6C. GLASS AREA TO MATCH PLANS. NEED TO
 INCLUDE ALL NEW WINDOWS AND EXISTING WINDOWS.
  
 D) REVISE ITEM #9. WALL TYPE DOESN'T MATCH PLANS.
  
 E) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND THE DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 OF CITY
 AMENDMENTS TO FBC. PROVIDE COPY OF SIGNED CONTRACT FOR
 THE CONSTRUCTION AND DESIGN PROFESSIONAL FEES. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 3- CLARIFY WHY SUBMITTING NOA 11-1013.14 FOR SINGLE
 HUNG WINDOWS. THERE IS NOT SINGLE HUNG WINDOWS ON THIS
 PROJECT. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- EXTERIOR BLOCK WALL SECTION 1/A.01:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH R-11 INSULATION ON A CONCRETE BLOCK
 WALL AS SPECIFIED ON THE WALL SECTION. NOTE: COORDINATE
 WITH THE ENERGY CALCULATIONS, INCLUDING THE CEILING R
 VALUE. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
 REVISED WALL SECTION DOESN'T COMPLY.
 R-VALUE GIVEN TO THE WALL IS FOR THE R-VALUE OF THE
 ADDED INSULATION ONLY. "THE R-VALUES OF STRUCTURAL
 BUILDING MATERIALS SUCH AS FRAMING MEMBERS, CONCRETE
 BLOCKS OR GYPSUM BOARD SHALL NOT BE INCLUDED.". SEE
 SEC. 304.1.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 NOTE: 3/4" DOW "TUFF-R" PROVIDES ONLY R-5 VALUE.
 PROVIDE ICC EVALUATION REPORT FOR THIS TYPE OF
 INSULATION SHOWING COMPLIANCE WITH SEC. R316. KEEP IN
 MIND THAT THIS PRODUCT IS USUALLY INSTALLED ON THE
 EXTERIOR SIDE OF THE WALL. SEE ESR-3089 REPORT. REVISE
 WALL SECTION DETAIL AS REQUIRED.
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  