2015-06-03 09:36:30 | RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- ENERGY CALCULATIONS SUBMITTED (SEC. 103.2.2 OF 2010 |
| FBC-ENERGY CONSERVATION). |
| A) FORM 402-2010 CAN NOT BE USED IF THE AIR HANDLER IS |
| LOCATED IN THE ATTIC. SEE GENERAL INSTRUCTIONS NOTE #1 |
| ON TOP OF FORM SUBMITTED. |
| |
| B) COMPLETE ALL THE INFORMATION ON TABLE 402A ON PAGE 2 |
| OF FORM SUBMITTED. THE INSTALLED VALUES MUST MEET OR |
| EXCEED THE PERFORMANCE CRITERIA. AND, REVISE ALL THE |
| INFORMATION ON PAGE ONE OF FORM SUBMITTED. SEE GENERAL |
| INSTRUCTION #2 ON TOP OF FORM SUBMITTED. |
| |
| C) REVISE ITEM #6C. GLASS AREA TO MATCH PLANS. NEED TO |
| INCLUDE ALL NEW WINDOWS AND EXISTING WINDOWS. |
| |
| D) REVISE ITEM #9. WALL TYPE DOESN'T MATCH PLANS. |
| |
| E) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| |
| 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND THE DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 OF CITY |
| AMENDMENTS TO FBC. PROVIDE COPY OF SIGNED CONTRACT FOR |
| THE CONSTRUCTION AND DESIGN PROFESSIONAL FEES. (REPEAT |
| COMMENT. NOT ADDRESSED). |
| |
| 3- CLARIFY WHY SUBMITTING NOA 11-1013.14 FOR SINGLE |
| HUNG WINDOWS. THERE IS NOT SINGLE HUNG WINDOWS ON THIS |
| PROJECT. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 4- EXTERIOR BLOCK WALL SECTION 1/A.01: |
| A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| COMPLIANCE WITH R-11 INSULATION ON A CONCRETE BLOCK |
| WALL AS SPECIFIED ON THE WALL SECTION. NOTE: COORDINATE |
| WITH THE ENERGY CALCULATIONS, INCLUDING THE CEILING R |
| VALUE. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| REVISED WALL SECTION DOESN'T COMPLY. |
| R-VALUE GIVEN TO THE WALL IS FOR THE R-VALUE OF THE |
| ADDED INSULATION ONLY. "THE R-VALUES OF STRUCTURAL |
| BUILDING MATERIALS SUCH AS FRAMING MEMBERS, CONCRETE |
| BLOCKS OR GYPSUM BOARD SHALL NOT BE INCLUDED.". SEE |
| SEC. 304.1.2 OF 2010 FBC-ENERGY CONSERVATION. |
| |
| NOTE: 3/4" DOW "TUFF-R" PROVIDES ONLY R-5 VALUE. |
| PROVIDE ICC EVALUATION REPORT FOR THIS TYPE OF |
| INSULATION SHOWING COMPLIANCE WITH SEC. R316. KEEP IN |
| MIND THAT THIS PRODUCT IS USUALLY INSTALLED ON THE |
| EXTERIOR SIDE OF THE WALL. SEE ESR-3089 REPORT. REVISE |
| WALL SECTION DETAIL AS REQUIRED. |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |