2015-03-13 16:08:25RESIDENTIAL (R3) GARAGE ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- CONVERTING GARAGE TO LIVING SPACE: BRING PLANS TO
 PALM BEACH COUNTY (2300 N. JOG RD) FOR IMPACT FEES
 ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4.3 OF 2010 FBC-ENERGY CONSERVATION AND SEC. 101.5
 OF 2010 FBC-EXISTING BUILDING.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND THE DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 OF CITY
 AMENDMENTS TO FBC. REVISE VALUATION AS REQUIRED. OR
 PROVIDE COPY OF SIGNED CONTRACT FOR THE CONSTRUCTION
 AND DESIGN PROFESSIONAL FEES.
  
 4- THESE PLANS ARE NOT TO BE USED FOR CONSTRUCTION. SEE
 STATEMENT AT THE BOTTOM LEFT OF SHEET A.01:
 "PRELIMINARY SET - NOT FOR CONSTRUCTION". PROVIDE PLANS
 THAT ARE READY FOR BUILDING PERMITS AND CONSTRUCTION.
 SEC. 107.2.1 CITY AMENDMENTS. TO FBC.
  
 5- ARCHITECT TO SPECIFY ALTERATION LEVEL TYPE AS
 REQUIRED BY SEC. 401.4 OF 2010 FBC EXISTING BUILDING.
  
 6- ARCHITECT TO PROVIDE INFORMATION SHOWING COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. R310 OF 2010
 FBC-RESIDENTIAL.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL WINDOW TYPES SPECIFIED ON PLANS.
  
 B) PRECAST LINTELS SPECIFIED ON NEW WINDOW/DOOR BUCK
 DETAIL.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 9- EXTERIOR BLOCK WALL SECTION 1/A.01:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH R-11 INSULATION ON A CONCRETE BLOCK
 WALL AS SPECIFIED ON THE WALL SECTION. NOTE: COORDINATE
 WITH THE ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 B) SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R302.11 OF
 2010 FBC-RESIDENTIAL.
  
 10- PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE
 WITH THE HEATING REQUIREMENTS OF SEC. R303.8 OF 2010
 FBC-RESIDENTIAL.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  