2015-03-13 16:08:25 | RESIDENTIAL (R3) GARAGE ALTERATION, BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- CONVERTING GARAGE TO LIVING SPACE: BRING PLANS TO |
| PALM BEACH COUNTY (2300 N. JOG RD) FOR IMPACT FEES |
| ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND COPY OF |
| PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY |
| IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| CODE. |
| |
| 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| 101.4.3 OF 2010 FBC-ENERGY CONSERVATION AND SEC. 101.5 |
| OF 2010 FBC-EXISTING BUILDING. |
| |
| 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND THE DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 OF CITY |
| AMENDMENTS TO FBC. REVISE VALUATION AS REQUIRED. OR |
| PROVIDE COPY OF SIGNED CONTRACT FOR THE CONSTRUCTION |
| AND DESIGN PROFESSIONAL FEES. |
| |
| 4- THESE PLANS ARE NOT TO BE USED FOR CONSTRUCTION. SEE |
| STATEMENT AT THE BOTTOM LEFT OF SHEET A.01: |
| "PRELIMINARY SET - NOT FOR CONSTRUCTION". PROVIDE PLANS |
| THAT ARE READY FOR BUILDING PERMITS AND CONSTRUCTION. |
| SEC. 107.2.1 CITY AMENDMENTS. TO FBC. |
| |
| 5- ARCHITECT TO SPECIFY ALTERATION LEVEL TYPE AS |
| REQUIRED BY SEC. 401.4 OF 2010 FBC EXISTING BUILDING. |
| |
| 6- ARCHITECT TO PROVIDE INFORMATION SHOWING COMPLIANCE |
| WITH THE EGRESS REQUIREMENTS OF SEC. R310 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) ALL WINDOW TYPES SPECIFIED ON PLANS. |
| |
| B) PRECAST LINTELS SPECIFIED ON NEW WINDOW/DOOR BUCK |
| DETAIL. |
| |
| 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 9- EXTERIOR BLOCK WALL SECTION 1/A.01: |
| A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| COMPLIANCE WITH R-11 INSULATION ON A CONCRETE BLOCK |
| WALL AS SPECIFIED ON THE WALL SECTION. NOTE: COORDINATE |
| WITH THE ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 |
| FBC-ENERGY CONSERVATION. |
| |
| B) SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R302.11 OF |
| 2010 FBC-RESIDENTIAL. |
| |
| 10- PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE |
| WITH THE HEATING REQUIREMENTS OF SEC. R303.8 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |