2015-02-07 07:16:53 | THE PLANS SHOW A WATER COOLER IN ROOM # 317. IF THE | | INTENT OF THIS WATER COOLER IS TO SATISFY THE PLUMBING | | CODE REQUIREMENT FOR A DRINKING FOUNTAIN PER TABLE | | 403.1 IT WILL NOT COMPLY. SEC.410.1 ALLOWS WATER | | COOLERS TO BE SUBSTITUTED FOR NOT MORE THAN 50% OF THE | | REQUIRED DRINKING FOUNTAINS. THE 2010 FBC | | -ACCESSIBILITY SEC.211.2 REQUIRES A MIN. OF 2 DRINKING | | FOUNTAINS.IF THERE ARE COMMON AREA DRINKING FOUNTAINS | | THAT COMPLY WITH THE ACCESSIBILITY CODE, INDICATE SUCH | | ON THE PLAN AND INDICATE THE LOCATION. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|