2015-02-24 15:45:33****CORRECTIONS****
 ****REVISED 2/26 AND EMAILED APPLICANT****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE SOFFIT OPTION SELECTED HAS A DP LIMITATION OF +?
 / -64.4 PSF. FOR 10SF (AREA TRIBUTARY TO A FASTENER),
 20' MRH, EXPOSURE D, DESIGN PRESSURES REQUIRED ARE
 +48.5/-52.6 FOR ZONE 4, AND +48.5/-65PSF FOR ZONE 5.
 CONTRACTOR HAS SELECTED A SYSTEM WHICH DOES NOT HAVE A
 POSITIVE DESIGN PRESSURE LIMITATION (PLEASE CONTACT
 MANUFACTURER OR INDICATE WHERE IN THE PRODUCT APPROVAL
 THIS IS ADDRESSED) AND DOES NOT MEET THE NEGATIVE
 PRESSURE FOR ZONE 5.
  
 OBTAINING THE EXACT MRH AND/OR OBTAINING ENGINEERING
 MAY RESULT IN LOWER PRESSURES.
  
 FBC 2010 RESIDENTIAL 301
  
 **PLEASE ADVISE VIA EMAIL WHEN THIS IS RESUBMITTED -
 REVIEW WILL BE DONE TIMELY**
  
 ***2/26 - NEGATIVE DP FOR MRH20', ZONE5, 169MPH IS
 -64.75PSF (DOES NOT MEET REQUIREMENT OF -64.4; PLEASE
 VERIFY MRH OR OBTAIN ENGINEERING)***
  