Plan Review Notes For Permit 15020119 |
Permit Number |
15020119 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-03-06 17:22:06 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PROVIDE A STRUCTURAL DETAIL FOR THE EXISTING SLAB, | | ANCHORING FOR PROPOSED FUEL TANK AND GENERATOR. SLAB TO | | RESIST DEAD LOADS, TANK AND GENERATOR TO RESIST SLIDING | | AND OVERTURNING CAUSED BY WIND LOADS, FBC 1609. | | | | |
|