Plan Review Notes For Permit 15020073 |
Permit Number |
15020073 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-03-10 10:34:59 | PLAN DENIED | | 1) PROVIDE DUCT SIZE ON PLAN, | | PROVIDE CAN AND GRILL SIZE ON PLAN | | PROVIDE CFM ON EACH SUPPLY DUCT. | | PER SECTION 107 FBC 2010 | | 2) SHOW LOCATION OF RETURN AIR ON PLANS. | | PER SECTION 107 FBC 2010 | | 3) REFER TO SECTION 601.4 BALANCED | | RETURN AIR 2010 FBC (M) | | 4) REFER TO SECTION 601.4 MATERIALS | | WITHIN PLENUM'S INCLUDING CLOSET DOOR | | AND CONDENSATE LINE 2010 FBC (M) | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | |
|