Plan Review Notes
Plan Review Notes For Permit 15020073
Permit Number 15020073
Review Stop M
Sequence Number 1
Notes
Date Text
2015-03-10 10:34:59PLAN DENIED
 1) PROVIDE DUCT SIZE ON PLAN,
 PROVIDE CAN AND GRILL SIZE ON PLAN
 PROVIDE CFM ON EACH SUPPLY DUCT.
 PER SECTION 107 FBC 2010
 2) SHOW LOCATION OF RETURN AIR ON PLANS.
 PER SECTION 107 FBC 2010
 3) REFER TO SECTION 601.4 BALANCED
 RETURN AIR 2010 FBC (M)
 4) REFER TO SECTION 601.4 MATERIALS
 WITHIN PLENUM'S INCLUDING CLOSET DOOR
 AND CONDENSATE LINE 2010 FBC (M)
  