Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-02-11 11:16:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PLANS WERE NOT STAPLED OR SEALED TOGETHER. THE
 PALNS SHALL BE SUBMITTED STAPLED OR SEALED TOGETHER TO
 NOT BE SEPARATED.
  
 SHEET C - 1 HAS AN INCORRECT ADDRESS IN THE ENGINEER
 COLUMN NOTED AS MIAMI, PLEASE DELETE AND CORRECT.
  
 SHEET C - 1 HAS THE INCORRECT EDITION OF THE FLORIDA
 FIRE PREVENTION CODE AS 2010. IT SHOULD INDICATE THE
 2012 EDITION OF NFPA 1 AND 101.
  
 ALL CONSTUCTION SHALL COMPLY WITH THE REQUIRMENTS OF
 NFPA 101, CHAPET 43, BUILDING REHABILITATION, SECTION
 43.6 RECONSTRUCTION.
  
 PER NFPA 101 43.6.4.1 IN A BUILDING WITH REHABILITATION
 WORK AREAS INVOLVING OVER 50 PERCENT OF THE AGGREGATE
 BUILDING AREA, AUTOMATIC SPRINKLER SYSTEMS SHALL BE
 PROVIDED ON THE HIGHEST FLOOR CONTAINING REHABILITATION
 WORK AREA AND ON ALL FLOORS BELOW IN ACCORDANCE WITH
 THE REQUIREMENTS OF OTHER SECTIONS OF THIS CODE
 APPLICABLE TO NEW CONTRUCTION FOR THE OCCUPANCY. THIS
 OCCUPANCY SHALL MEET THE REQUIREMENTS OF NFPA 101,
 CHAPTER 30 NEW APARTMENT BUILDINGS.THE FIRE SPRINKLER
 SYSTEM SHALL BE SUPERVISED PER NFPA 30.
  
 PER SECTION 43.6.2.2 ILLUMINATION, EMERGENCY LIGHTING
 AND MARKING OF MEANS OF EGRESS, 43.6.2.2.2 WHERE THE
 RECONSTRUCTION REHABILITATION WORK AREA ON ANY FLOOR
 EXCEEDS 50 PERCENT OF THEAT FLOOR AREA, MEANS OF EGRESS
 THROUGHOUT THE FLOOR SHALL BE PROVIDED WITH
 ILLUMINATION, EMERGENCY LIGHTING AND MARKING OF MEANS
 OF EGRESS IN ACCORDANCE WITH THE REQUIREMENTS OF OTHER
 SECTIONS OF THIS CODE APPLICABLE TO NEW CONTRUCTION FOR
 THE OCCUPANCY.
  
 PER SECTION 43.6.5 FIRE ALARM SYSTEMS - SMOKE ALARMS,
 43.6.5.1 IN LODGING OR ROOMING HOUSES, HOTELS, AND
 DORMITORIES, AND APARTMENT BUILDINGS, INDIVIDUAL
 SLEEPING ROOMS, GUEST ROOMS, AND DWELLING UNITS WITHIN
 REHABILITATION WORK AREA SHALL BE PROVIDED WITH SMOKE
 ALARMS COMPLYING WITH THE REQUIRMENTS OF OTHER SECTIONS
 OF THIS CODE APPLICABLE TO NEW CONSTRUCTION FOR THE
 OCCUPANCY.
  
 THE CONSTUCTION SHALL COMPLY WITH NFPA 101, CHAPTER 30,
 NEW APARTMENT BUILDINGS.
  
 EMERGENCY LIGHTING IS REQUIRED AT EACH PORCH AREA. EXIT
 SIGNAGE IS REQUIRED AT THE SECOND FLOOR LEVEL PORCH
 AREA.
  
 EACH ENTRY DOOR IN THE FIRST AND SECOND FLOOR AREA IS
 REQUIRED TO HAVE NOT LESS THAN A 20 MINUTE FIRE
 PROTECTION RATING AND SHALL BE SELF CLOSING AND
 LATCHING.
  
  
  
  
  
  
  