2015-02-11 11:16:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| THE PLANS WERE NOT STAPLED OR SEALED TOGETHER. THE |
| PALNS SHALL BE SUBMITTED STAPLED OR SEALED TOGETHER TO |
| NOT BE SEPARATED. |
| |
| SHEET C - 1 HAS AN INCORRECT ADDRESS IN THE ENGINEER |
| COLUMN NOTED AS MIAMI, PLEASE DELETE AND CORRECT. |
| |
| SHEET C - 1 HAS THE INCORRECT EDITION OF THE FLORIDA |
| FIRE PREVENTION CODE AS 2010. IT SHOULD INDICATE THE |
| 2012 EDITION OF NFPA 1 AND 101. |
| |
| ALL CONSTUCTION SHALL COMPLY WITH THE REQUIRMENTS OF |
| NFPA 101, CHAPET 43, BUILDING REHABILITATION, SECTION |
| 43.6 RECONSTRUCTION. |
| |
| PER NFPA 101 43.6.4.1 IN A BUILDING WITH REHABILITATION |
| WORK AREAS INVOLVING OVER 50 PERCENT OF THE AGGREGATE |
| BUILDING AREA, AUTOMATIC SPRINKLER SYSTEMS SHALL BE |
| PROVIDED ON THE HIGHEST FLOOR CONTAINING REHABILITATION |
| WORK AREA AND ON ALL FLOORS BELOW IN ACCORDANCE WITH |
| THE REQUIREMENTS OF OTHER SECTIONS OF THIS CODE |
| APPLICABLE TO NEW CONTRUCTION FOR THE OCCUPANCY. THIS |
| OCCUPANCY SHALL MEET THE REQUIREMENTS OF NFPA 101, |
| CHAPTER 30 NEW APARTMENT BUILDINGS.THE FIRE SPRINKLER |
| SYSTEM SHALL BE SUPERVISED PER NFPA 30. |
| |
| PER SECTION 43.6.2.2 ILLUMINATION, EMERGENCY LIGHTING |
| AND MARKING OF MEANS OF EGRESS, 43.6.2.2.2 WHERE THE |
| RECONSTRUCTION REHABILITATION WORK AREA ON ANY FLOOR |
| EXCEEDS 50 PERCENT OF THEAT FLOOR AREA, MEANS OF EGRESS |
| THROUGHOUT THE FLOOR SHALL BE PROVIDED WITH |
| ILLUMINATION, EMERGENCY LIGHTING AND MARKING OF MEANS |
| OF EGRESS IN ACCORDANCE WITH THE REQUIREMENTS OF OTHER |
| SECTIONS OF THIS CODE APPLICABLE TO NEW CONTRUCTION FOR |
| THE OCCUPANCY. |
| |
| PER SECTION 43.6.5 FIRE ALARM SYSTEMS - SMOKE ALARMS, |
| 43.6.5.1 IN LODGING OR ROOMING HOUSES, HOTELS, AND |
| DORMITORIES, AND APARTMENT BUILDINGS, INDIVIDUAL |
| SLEEPING ROOMS, GUEST ROOMS, AND DWELLING UNITS WITHIN |
| REHABILITATION WORK AREA SHALL BE PROVIDED WITH SMOKE |
| ALARMS COMPLYING WITH THE REQUIRMENTS OF OTHER SECTIONS |
| OF THIS CODE APPLICABLE TO NEW CONSTRUCTION FOR THE |
| OCCUPANCY. |
| |
| THE CONSTUCTION SHALL COMPLY WITH NFPA 101, CHAPTER 30, |
| NEW APARTMENT BUILDINGS. |
| |
| EMERGENCY LIGHTING IS REQUIRED AT EACH PORCH AREA. EXIT |
| SIGNAGE IS REQUIRED AT THE SECOND FLOOR LEVEL PORCH |
| AREA. |
| |
| EACH ENTRY DOOR IN THE FIRST AND SECOND FLOOR AREA IS |
| REQUIRED TO HAVE NOT LESS THAN A 20 MINUTE FIRE |
| PROTECTION RATING AND SHALL BE SELF CLOSING AND |
| LATCHING. |
| |
| |
| |
| |
| |
| |
| |