2015-02-05 11:02:322/5/2015
 PROJECT: 513 SAPODILLA
 PERMIT#: 15020073
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) CHANGE TITLE BLOCK ON COVER SHEET TO CORRECT THE
 PROJECT ADDRESS. WPB AMENDMENTS TO FBC 107.2.1
  
 2) PROVIDE FAULT CURRENT RATING CALCULATION AND VERIFY
 THE ELECTRICAL SERVICE HAS A FAULT CURRENT RATING THAT
 IS SUFFICIENT AT NOMINAL CIRCUIT VOLTAGE FOR THE
 CURRENT THAT MUST BE INTERRUPTED. NEC 110.9
  
 3) PROVIDE CIRCUIT NUMBERS ON THE FLOOR PLAN
 CORESPONDING TO THE PANEL DIRECTORY. WPB AMENDMENTS TO
 FBC 107.2.1
  
 4) PROVIDE DISCONNECTS WHERE REQUIRED FOR EQUIPMERNT
 SUCH AS WATER HEATER AND AHU. WPB AMENDMENTS TO FBC
 107.2.1
  
 5) PROVIDE SMOKE ALARMS LOCATED AS REQUIRED FOR NEW
 DWELLINGS. SMOKE DETECTOR REQUIRED OUTSIDE OF SLEEPING
 ROOMS. FBC-RESIDENTIAL 314 AND 315.
  
 6) ADD A NOTE FOR THE LUMINAIRES IN CLOTHES CLOSETS
 SHALL BE INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF
 THE NEC 410.16(A) AND (B).
  
 7) PROVIDE A LIGHT FOR THE STAIRS THAT CAN BE CONTROLED
 FROM THE TOP OR BOTTOM LANDINGS. FBC 1205.4, 1205.5,
 1006.1, NEC 210.70
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  