2015-02-27 08:15:26 | BUILDING PLAN REVIEW |
| PERMIT: 15020073 |
| ADD: 513 N. SAPODILLA AVE. |
| CONT: MISO CONSTRUCTION |
| TEL: ( 561)246-0411 |
| E-MAIL:[email protected] |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| IMPORTANT NOTICE: EFFECTIVE MAY 11, 2015 |
| ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| ELECTRONICALLY |
| UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| SUBMISSION OPTIONS ARE AS FOLLOWS: |
| 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL |
| SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| NAMING CONVENTION FOR EACH DOCUMENT |
| 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| AVAILABLE |
| |
| |
| 1ST REVIEW |
| DATE: FRI. FEB. 27/ 2015 |
| ACTION: DENIED |
| |
| 1) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) WALL LOUVERS, |
| (E) SHUTTERS/ IF WINDOWS ARE NOT IMPACT RESISTANT |
| TESTED |
| |
| 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 3) THE COVERSHEET INDICATE THIS IS A LEVEL LL |
| ALTERATION AND DRYWALL IS TO BE PATCHED, THE PLANS DOES |
| NOT PROVIDE AS TO HOW MUCH IN AREA THIS DRYWALL PATCH |
| WORK WILL BE, SECTION 703.4.1 OF THE EXST. BLDG. CODE |
| MAY APPLY. 703.4.1 SUPPLEMENTAL INTERIOR FINISH |
| REQUIREMENTS. |
| WHERE THE WORK AREA ON ANY FLOOR EXCEEDS 50 PERCENT OF |
| THE FLOOR AREA, SECTION 703.4 SHALL ALSO APPLY TO THE |
| INTERIOR FINISH IN EXITS AND CORRIDORS SERVING THE WORK |
| AREA THROUGHOUT THE FLOOR. |
| |
| 4) THE PLANS DO NOT INDICATE WHERE THE WORK AREA IS |
| CLEARLY, DOES THE GUARDRAILS COMPLY WITH EXST. BLDG. |
| CODE 703.5. |
| |
| 5) SHEET A-2 LIST THIS PROJECT AS A R-3 OCCUPANCY, SEE |
| WIND DESIGN, PLEASE REVISE 2010 FBC-B 310.1 R-2. |
| APARTMENT HOUSES. |
| |
| 6) SHEET A-1 1ST FLOOR VERSES SHEET A-3 THE 2ND FLOOR, |
| THE 1ST FLOOR SHOWS DROPPED CEILINGS TO RUN THE A/C |
| DUCT, THE 2ND FLOOR PLANS DO NOT SHOW A HATCHED AREA |
| BUT IT APPEARS ON THE 2ND FLOOR MECHANICAL SOME OF THE |
| A/C DROPS WILL BE SIDE WALL WHERE OTHERS WILL BE |
| CEILING GRILLES. 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED, MAY BE A DISSCREPANCY IN THE PLANS. |
| |
| 7) SHEET A-3 NOTES TENANT SEPARATION WALL INDICATES IN |
| NOTE # 1 SOUND INSULATION IS REQUIRED FOR THE TENANT |
| SEPARATION WALL. PLEASE PROVIDE COMPLIANCE WITH 2010 |
| FBC-B 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND |
| FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM |
| EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 |
| IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN |
| ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS IN |
| CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; |
| RECESSED CABINETS; BATHTUBS; SOFFITS; OR HEATING, |
| VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, LINED, |
| INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED |
| RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO DWELLING |
| UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| FITTING TO THE FRAME AND SILL. |
| |
| 8) THE PLANS WILL ALSO NEED ON THE 2ND FLOOR, FLOOR |
| SYSTEM TO SHOW COMPLIANCE WITH 2010 FBC-B 1207.3 |
| STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. |
| |
| 9) A-3 FLOOR FINISHES SHOW CARPET FOR ALL FLOORS, WILL |
| THERE BE CARPET IN THE BATHROOMS AND KITCHEN AREAS AS |
| WELL? THE PLANS ARE NOT CLEAR IF DRYWALL IS BEING |
| REPLACED IN THE SHOWER COMPARTMENTS AS WELL? 107.2.1.3. |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 10) PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1209.2 ATTIC |
| SPACES. |
| AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM |
| BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A |
| CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762 |
| MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE |
| PROVIDED AT OR ABOVE THE ACCESS OPENING. |
| |
| 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |