2015-06-24 14:26:56 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| THE CORRECTIONS NOTED. |
| THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS |
| RESUBMITTED FOR A SECOND REVIEW: |
| |
| 1. PER NFPA 72 ? 29.8.3.4(4), SMOKE DETECTORS SHALL NOT |
| BE INSTALLED WITHIN 3? FROM THE TIP OF A CEILING FAN |
| BLADE OR ANY OTHER SOURCE OF FORCED AIR (A/C VENT OR |
| RETURN). |
| 2. PER FBC-R ? 315, YOU SHALL INSTALL A CO (CARBON |
| MONOXIDE) DETECTOR WITHIN 10? OF THE BEDROOM DOOR. |
| THEREFORE THE CEILING DETECTOR IN THE VESTIBULE OUTSIDE |
| THE BEDROOMS SHALL BE A COMBINATION UNIT. |
| 3. PER NEC 230.70, YOU SHALL HAVE A DISCONNECT ON THE |
| OUTSIDE OF THE STRUCTURE OR AT A POINT NEAREST THE |
| ENTRY THERETO. IN YOUR CASE ADJACENT TO THE SERVICE |
| METER WILL DO. |
| 4. PER NEC 440.14, THE DISCONNECT FOR THE RELOCATED AHU |
| SHALL BE READILY ACCESSIBLE. |
| 5. CONFIRM THE NEED FOR ?NOTE 21?, OF THE GENERAL |
| NOTES. |
| 6. CORRECT CONDUCTOR INSULATION AS INDICATED ON ?NOTE |
| 28? OF GENERAL NOTES. |
| 7. CORRECT THE RISER DIAGRAMS TO INCLUDE THE REQUIRED |
| SERVICE DISCONNECT AND RENAME PANEL ?A? AS ?RELOCATED? |
| RATHER THAN ?EXISTING?. |
| 8. CORRECT ?NOTE 2? OF NOTE (). |
| 9. PER NEC 210.52(C), THE KITCHEN OUTLETS ARE INDICATED |
| ON THE DRAWING ARE NOT COMPLIANT WITH MINIMUM CODE |
| REQUIREMENTS. |
| |