Plan Review Notes
Plan Review Notes For Permit 15020068
Permit Number 15020068
Review Stop E
Sequence Number 3
Notes
Date Text
2015-06-24 14:26:56PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED.
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
 1. PER NFPA 72 ? 29.8.3.4(4), SMOKE DETECTORS SHALL NOT
 BE INSTALLED WITHIN 3? FROM THE TIP OF A CEILING FAN
 BLADE OR ANY OTHER SOURCE OF FORCED AIR (A/C VENT OR
 RETURN).
 2. PER FBC-R ? 315, YOU SHALL INSTALL A CO (CARBON
 MONOXIDE) DETECTOR WITHIN 10? OF THE BEDROOM DOOR.
 THEREFORE THE CEILING DETECTOR IN THE VESTIBULE OUTSIDE
 THE BEDROOMS SHALL BE A COMBINATION UNIT.
 3. PER NEC 230.70, YOU SHALL HAVE A DISCONNECT ON THE
 OUTSIDE OF THE STRUCTURE OR AT A POINT NEAREST THE
 ENTRY THERETO. IN YOUR CASE ADJACENT TO THE SERVICE
 METER WILL DO.
 4. PER NEC 440.14, THE DISCONNECT FOR THE RELOCATED AHU
 SHALL BE READILY ACCESSIBLE.
 5. CONFIRM THE NEED FOR ?NOTE 21?, OF THE GENERAL
 NOTES.
 6. CORRECT CONDUCTOR INSULATION AS INDICATED ON ?NOTE
 28? OF GENERAL NOTES.
 7. CORRECT THE RISER DIAGRAMS TO INCLUDE THE REQUIRED
 SERVICE DISCONNECT AND RENAME PANEL ?A? AS ?RELOCATED?
 RATHER THAN ?EXISTING?.
 8. CORRECT ?NOTE 2? OF NOTE ().
 9. PER NEC 210.52(C), THE KITCHEN OUTLETS ARE INDICATED
 ON THE DRAWING ARE NOT COMPLIANT WITH MINIMUM CODE
 REQUIREMENTS.
  