2015-03-16 09:44:26 | 3/16/2015 |
| PROJECT: CONVERT STUDY BACK INTO GARAGE |
| PERMIT#: 15020068 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) NEC 408.4 |
| PROVIDE A PANEL SCHEDULE TO INDICATE ALL CIRCUITRY |
| INVOLVED IN CONVERSION. EVERY CIRCUIT AND CIRCUIT |
| MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS |
| CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4 |
| |
| 2) FBC 107 |
| INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN WITH |
| CORRESPONDING OCPD AND WIRE SIZE AS INDICATED ION THE |
| PANEL SCHEDULE. FBC 107 |
| |
| 3) NEC 210.8 |
| INDICATE ALL OUTLETS IN THE GARAGE TO BE GFI PROTECTED. |
| INCLUDING THE GARAGE DOOR OPENER OUTLET. NEC 210.8 |
| |
| 4) NEC 210.12, 406.11 |
| ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| |
| 5) FBC-RESIDENTIAL 314 AND 315. |
| WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. ADD SMOKE AND CO |
| DETECTOR OUTSIDE OF SLEEPING AREAS. FBC-RESIDENTIAL 314 |
| AND 315. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |