2015-02-19 16:39:44BUILDING PLAN REVIEW
 PERMIT: 15020066
 ADD: 1551 N FLAGLER DR
 CONT: BLUE OCEAN
 TEL: (561)201-6206
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE ????, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: THURS. FEB. 19/ 2015
 ACTION: DENIED
  
 1) THE PLANS INDICATE TO DEMO CMU BLOCK, IN-FILL UP TO
 THE CONCRETE TIE BEAM ABOVE. PLEASE PROVIDE DETAIL FOR
 THE COLUMNS AND LINTEL FOR THE IN-FILL BLOCK TO REST ON
 AS WELL AS TIE THE FIRE RATED DOORS AND FRAME TO
 INTERLOCK INTO.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 STRUCTURAL REQUIREMENTS SHALL INCLUDE:WALL SYSTEMS
 2101.2 DESIGN METHODS.
 2101.3 CONSTRUCTION DOCUMENTS.
 THE CONSTRUCTION DOCUMENTS SHALL SHOW ALL OF THE ITEMS
 REQUIRED BY THIS CODE INCLUDING THE FOLLOWING:
  
 1. SPECIFIED SIZE, GRADE, TYPE AND LOCATION OF
 REINFORCEMENT, ANCHORS AND WALL TIES.
  
 2. REINFORCING BARS TO BE WELDED AND WELDING PROCEDURE.
  
 3. SIZE AND LOCATION OF STRUCTURAL ELEMENTS.
  
 4. PROVISIONS FOR DIMENSIONAL CHANGES RESULTING FROM
 ELASTIC DEFORMATION, CREEP, SHRINKAGE, TEMPERATURE AND
 MOISTURE.
  
 5. LOADS USED IN THE DESIGN OF MASONRY.
  
 6. SPECIFIED COMPRESSIVE STRENGTH OF MASONRY AT STATED
 AGES OR STAGES OF CONSTRUCTION FOR WHICH MASONRY IS
 DESIGNED, EXCEPT WHERE
 SPECIFICALLY EXEMPTED BY THIS CODE.
  
 7. DETAILS OF ANCHORAGE OF MASONRY TO STRUCTURAL
 MEMBERS, FRAMES AND OTHER CONSTRUCTION, INCLUDING THE
 TYPE, SIZE AND LOCATION OF
 CONNECTORS.
  
 2) THE APPLIED VALUE OF THIS JOB IS EXTREMELY
 LOW!!!!!!!!!
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) THE CONTRACTOR SIGNATURE/ PRINT NAME IS SHOWN AS
 AMMON THAUR, THIS IS NOT THE QUALIFIER FOR BLUE OCEAN
 CONTRACTORS, THE QUALIFIER AS WELL AS THE OWNERS WILL
 NEED TO SIGN AND NOTIRIZE A NEW PERMIT APPLICATION.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  