Plan Review Notes For Permit 15020033 |
Permit Number |
15020033 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-03-03 09:22:06 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD. PROVIDE SUBMITTALS FOR THE FIXED | | GLASS WINDOW AND THE STRUCTURAL MULLIONS. | | | | 2) THE SCOPE OF WORK ON THE APPLICATION INCLUDES THE | | UPGRADE OF THE ELECTRICAL PANEL, HOWEVER, NO ELECTRIC | | WORK WAS SHOWN ON THE PLANS. PLEASE CLARIFY. FBC | | 107.2.1 |
|