2015-05-20 17:00:35 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1- PROVIDE DRAWINGS THAT MATCH SHEET INDEX ON SHEET |
| A-0. |
| 2- WINDOWS ON SECOND FLOOR THAT HAVE WINDOW SILL LESS |
| THAN 24" FROM FINISHED FLOOR OF THAT ROOM NEED TO |
| COMPLY WITH THE FALL PREVENTION REQUIREMENTS OF SEC. |
| R612.2. PROVIDE SPECIFICATIONS SHOWING COMPLIANCE. |
| 3- REVISE HANDRAIL AND GUARDRAILS DETAILS. PROVIDE |
| COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| CONSTRUCTION AND INSTALLATION OF HANDRAILS AND |
| GUARDRAILS SHOWING COMPLIANCE WITH THE LIVE LOADS OF |
| TABLE R301.5, SEC. R311.7.7 AND SEC. R312 OF 2010 |
| FBC-RESIDENTIAL. |
| SPECIFY ALL FRAMING MEMBERS MATERIALS AND CONNECTORS. |
| RAILING DETAIL SHOWN ON THE LEFT HAND SIDE DOESN'T |
| MATCH ELEVATION ON THE RIGHT HAND SIDE. |
| 4-REVISE STEEL COLUMN DETAIL. SIZE TO-MATCH PLANS. |
| CLEARLY SPECIFY TOP & BOTTOM CONNECTORS AND FASTENERS |
| THAT MATCH ACTUAL FIELD CONDITIONS. SPECIFY BEAM SIZE. |
| 5- PROVIDE FLOOR FRAMING DETAILS FOR NEW 2ND FLOOR |
| W-I-C. |
| 6- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FRENCH DOORS |
| WITH SIZES AS SHOWN ON PLANS FOR ALL DOORS. |
| 7- REVISE THE WIND LOADS SHOWN ON THE EXTERIOR |
| ELEVATIONS (SHEET A2 OR A3). REVISE EXPOSURE TO "D" AS |
| SHOWN ON SHEET A0. AND REVISE THE DESIGN PRESSURES |
| ACCORDINGLY. ALSO. KEY CORRECTLY THE "A" AND "B" |
| WINDOWS/DOORS ON THE ELEVATIONS. |