Plan Review Notes
Plan Review Notes For Permit 15020030
Permit Number 15020030
Review Stop B
Sequence Number 4
Notes
Date Text
2015-05-20 17:00:35BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE DRAWINGS THAT MATCH SHEET INDEX ON SHEET
 A-0.
 2- WINDOWS ON SECOND FLOOR THAT HAVE WINDOW SILL LESS
 THAN 24" FROM FINISHED FLOOR OF THAT ROOM NEED TO
 COMPLY WITH THE FALL PREVENTION REQUIREMENTS OF SEC.
 R612.2. PROVIDE SPECIFICATIONS SHOWING COMPLIANCE.
 3- REVISE HANDRAIL AND GUARDRAILS DETAILS. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF HANDRAILS AND
 GUARDRAILS SHOWING COMPLIANCE WITH THE LIVE LOADS OF
 TABLE R301.5, SEC. R311.7.7 AND SEC. R312 OF 2010
 FBC-RESIDENTIAL.
 SPECIFY ALL FRAMING MEMBERS MATERIALS AND CONNECTORS.
 RAILING DETAIL SHOWN ON THE LEFT HAND SIDE DOESN'T
 MATCH ELEVATION ON THE RIGHT HAND SIDE.
 4-REVISE STEEL COLUMN DETAIL. SIZE TO-MATCH PLANS.
 CLEARLY SPECIFY TOP & BOTTOM CONNECTORS AND FASTENERS
 THAT MATCH ACTUAL FIELD CONDITIONS. SPECIFY BEAM SIZE.
 5- PROVIDE FLOOR FRAMING DETAILS FOR NEW 2ND FLOOR
 W-I-C.
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FRENCH DOORS
 WITH SIZES AS SHOWN ON PLANS FOR ALL DOORS.
 7- REVISE THE WIND LOADS SHOWN ON THE EXTERIOR
 ELEVATIONS (SHEET A2 OR A3). REVISE EXPOSURE TO "D" AS
 SHOWN ON SHEET A0. AND REVISE THE DESIGN PRESSURES
 ACCORDINGLY. ALSO. KEY CORRECTLY THE "A" AND "B"
 WINDOWS/DOORS ON THE ELEVATIONS.