2015-05-16 06:03:591) SHT.A-0 - SHEET INDEX LISTS SHEETS A-0,D-1, A-1,
 A-2, A-3,E-1. SHTS.D-1, A-1, & A-3 ARE NOT IN THESE SET
 OF PLANS. CLARIFY.
 2)) AS DRAWN, THE SANITARY RISER FOR THE 2ND FLOOR DOES
 NOT MEET THE2010 FBC-R CODE SEC. P3108.1 FOR A
 HORIZONTAL WET VENT. THE HORIZONTAL WET VENT HAS TOO
 MANY FIXTURES ON IT PER THE DEFINITION OF A "BATHROOM
 GROUP." NOT MORE THAN TWO FIXTURES OF ANY TYPE CAN BE
 CONNECTED TO THE WET VENT SYSTEM.
 NOTE: YOU MAY WANT TO CONTACT ME TO SET UP AN
 APPOINTMENT WITH ME TO REVIEW THE RISER DIAGRAM.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR