Plan Review Notes For Permit 15020030 |
Permit Number |
15020030 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-04-04 10:39:28 | 1) THE BATH FOR BEDROOM NUMBER 4 IS NOT SHOWN ON THE | | 2ND FLOOR RISER DIAGRAM.WPB AMEND. TO 2010 FBC SEC. | | 107.3.5.1.3. | | 2) AS DRAWN, THE SANITARY RISER FOR THE 2ND FLOOR DOES | | NOT MEET CODE. THE HORIZONTAL WET VENT HAS ONE TOO MANY | | LAVATORIES, ONE TOO MANY SHOWERS AND EXCEEDS THE | | MAXIMUM NUMBER OF FIXTURE UNITS FOR A 2" WET VENT PER | | TABLE P3108.3 OF THE 2010 FBCR SEC. P3108. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|