2015-04-10 11:05:22RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PHASE 2 OF THIS PROJECT (WINDOWS AND DOORS) WAS
 ADDED ON 3/11/15. PLEASE UPDATE VALUATION DECLARED IN
 THE PERMIT APPLICATION AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS TO FBC. PLEASE PROVIDE COPY OF SIGNED
 CONTRACT FOR THE OVERALL SCOPE OF WORK.
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- SHEET A-2:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 NEW HANDRAILS AND GUARDRAILS SHOWING COMPLIANCE WITH
 ALL THE REQUIREMENTS OF SEC. R311.7.7 AND SEC. R312 OF
 2010 FBC-RESIDENTIAL. ALSO, PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE LIVE
 LOAD REQUIREMENTS OF TABLE R301.5 OF 2010
 FBC-RESIDENTIAL. REPEAT COMMENT. "GUARDRAIL/HANDRAIL
 DETAILS" SUBMITTED DOESN'T MATCH PLANS. THERE ARE NOT
 DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE
 HANDRAIL AND GUARDRAIL SHOWING COMPLIANCE WITH THE LIVE
 LOAD OF TABLE R301.5. GUARDRAIL HEIGHT IS DIMENSIONED
 AS 36", WHILE GUARDRAIL NOTE STATES 42". REVISE AS
 REQUIRED TO MATCH. SEC. 1608.2 SPECIFIED ON GUARDRAIL
 DETAIL DOESN'T APPLY TO SINGLE FAMILY RESIDENCE (R3).
 THAT SECTIONS APPLIES TO THE BUILDING CODE NOT THE
 RESIDENTIAL CODE. BESIDES THAT SECTION IS "RESERVED".
 REVISE AS REQUIRED.
  
 3- PROVIDE COMPLETE SHORING DETAILS AND SPECIFICATIONS
 FOR THE INSTALLATION OF THE NEW STEEL COLUMNS. SEC.
 107.2.1.3 CITY AMENDMENTS. REPEAT COMMENT. NOT
 ADDRESSED.
  
 4- PROVIDE PRODUCT APPROVAL (TWO COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOW MULLIONS. PROVIDE PRODUCT APPROVAL FOR BAY
 WINDOWS MULLIONS. AS SHOWN ON PLANS. FLORIDA PRODUCT
 APPROVAL FL15922 SUBMITTED IS FOR STRAIGHT MULLIONS
 ONLY. AND, CLEARLY SPECIFY MULLION SIZE FOR ALL WINDOWS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.
 NOTE: AS AN ALTERNATIVE YOU CAN SUBMIT PRODUCT APPROVAL
 FOR COMPLETE BAY WINDOWS ASSEMBLY AS SHOWN ON PLANS.
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) THERE WAS INFORMATION SUBMITTED FOR CASEMENT
 WINDOWS. PLANS AND NEW WINDOW SCHEDULE DON'T SHOW
 CASEMENT WINDOWS. CLARIFY/REVISE AS REQUIRED. IF
 CASEMENT WINDOWS WILL BE INSTALLED, THEN PROVIDE THE
 APPROVED FLORIDA PRODUCT APPROVAL NUMBER THAT
 CORRESPOND TO INFORMATION SUBMITTED. IF THERE IS NONE,
 THEN MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL.
 REPEAT COMMENT. NOT ADDRESSED.
  
 C) NEED TWO COPIES OF DOUBLE HUNG PRODUCT APPROVALS.
 ONLY ONE WAS SUBMITTED. REPEAT COMMENT. NOT ADDRESSED.
  
 D) FRENCH DOORS WITH SIZES AS SHOWN ON PLANS FOR DOORS
 #1 AND #8. . NOTE: FLORIDA PRODUCT APPROVAL FL14285
 SUBMITTED IS NOT ACCEPTABLE. ALL THE CHARTS WERE
 BLOCKED OUT. PRODUCT APPROVAL CAN NOT BE ALTERED.
 PROVIDE COMPLETE PRODUCT APPROVAL AND PROVIDE PRODUCT
 APPROVAL THAT COVERS DOORS #1 AND #8. REPEAT COMMENT.
 NOT ADDRESSED.
  
 E) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED
 ON ALL DETAILS ON SHEET A-4. NOTE: PROVIDE ONLY THE
 FLORIDA PRODUCT APPROVAL FRONT PAGE AND PAGE SHOWING
 THE SPECIFIED CONNECTOR OR LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO THE SPECIFIED CONNECTOR. REPEAT
 COMMENT. NOT ADDRESSED.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVAL. SEC. 107.3.4.1 CITY AMENDMENTS.
 REPEAT COMMENT. NOT ADDRESSED.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED SHEET AND
 SUBMIT OLD PLANS FOR REFERENCE.
  