2015-04-10 11:05:22 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- PHASE 2 OF THIS PROJECT (WINDOWS AND DOORS) WAS |
| ADDED ON 3/11/15. PLEASE UPDATE VALUATION DECLARED IN |
| THE PERMIT APPLICATION AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS TO FBC. PLEASE PROVIDE COPY OF SIGNED |
| CONTRACT FOR THE OVERALL SCOPE OF WORK. |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 2- SHEET A-2: |
| A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| NEW HANDRAILS AND GUARDRAILS SHOWING COMPLIANCE WITH |
| ALL THE REQUIREMENTS OF SEC. R311.7.7 AND SEC. R312 OF |
| 2010 FBC-RESIDENTIAL. ALSO, PROVIDE COMPLETE DETAILS |
| AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE LIVE |
| LOAD REQUIREMENTS OF TABLE R301.5 OF 2010 |
| FBC-RESIDENTIAL. REPEAT COMMENT. "GUARDRAIL/HANDRAIL |
| DETAILS" SUBMITTED DOESN'T MATCH PLANS. THERE ARE NOT |
| DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE |
| HANDRAIL AND GUARDRAIL SHOWING COMPLIANCE WITH THE LIVE |
| LOAD OF TABLE R301.5. GUARDRAIL HEIGHT IS DIMENSIONED |
| AS 36", WHILE GUARDRAIL NOTE STATES 42". REVISE AS |
| REQUIRED TO MATCH. SEC. 1608.2 SPECIFIED ON GUARDRAIL |
| DETAIL DOESN'T APPLY TO SINGLE FAMILY RESIDENCE (R3). |
| THAT SECTIONS APPLIES TO THE BUILDING CODE NOT THE |
| RESIDENTIAL CODE. BESIDES THAT SECTION IS "RESERVED". |
| REVISE AS REQUIRED. |
| |
| 3- PROVIDE COMPLETE SHORING DETAILS AND SPECIFICATIONS |
| FOR THE INSTALLATION OF THE NEW STEEL COLUMNS. SEC. |
| 107.2.1.3 CITY AMENDMENTS. REPEAT COMMENT. NOT |
| ADDRESSED. |
| |
| 4- PROVIDE PRODUCT APPROVAL (TWO COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) WINDOW MULLIONS. PROVIDE PRODUCT APPROVAL FOR BAY |
| WINDOWS MULLIONS. AS SHOWN ON PLANS. FLORIDA PRODUCT |
| APPROVAL FL15922 SUBMITTED IS FOR STRAIGHT MULLIONS |
| ONLY. AND, CLEARLY SPECIFY MULLION SIZE FOR ALL WINDOWS |
| TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| R301. |
| NOTE: AS AN ALTERNATIVE YOU CAN SUBMIT PRODUCT APPROVAL |
| FOR COMPLETE BAY WINDOWS ASSEMBLY AS SHOWN ON PLANS. |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| B) THERE WAS INFORMATION SUBMITTED FOR CASEMENT |
| WINDOWS. PLANS AND NEW WINDOW SCHEDULE DON'T SHOW |
| CASEMENT WINDOWS. CLARIFY/REVISE AS REQUIRED. IF |
| CASEMENT WINDOWS WILL BE INSTALLED, THEN PROVIDE THE |
| APPROVED FLORIDA PRODUCT APPROVAL NUMBER THAT |
| CORRESPOND TO INFORMATION SUBMITTED. IF THERE IS NONE, |
| THEN MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL. |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| C) NEED TWO COPIES OF DOUBLE HUNG PRODUCT APPROVALS. |
| ONLY ONE WAS SUBMITTED. REPEAT COMMENT. NOT ADDRESSED. |
| |
| D) FRENCH DOORS WITH SIZES AS SHOWN ON PLANS FOR DOORS |
| #1 AND #8. . NOTE: FLORIDA PRODUCT APPROVAL FL14285 |
| SUBMITTED IS NOT ACCEPTABLE. ALL THE CHARTS WERE |
| BLOCKED OUT. PRODUCT APPROVAL CAN NOT BE ALTERED. |
| PROVIDE COMPLETE PRODUCT APPROVAL AND PROVIDE PRODUCT |
| APPROVAL THAT COVERS DOORS #1 AND #8. REPEAT COMMENT. |
| NOT ADDRESSED. |
| |
| E) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED |
| ON ALL DETAILS ON SHEET A-4. NOTE: PROVIDE ONLY THE |
| FLORIDA PRODUCT APPROVAL FRONT PAGE AND PAGE SHOWING |
| THE SPECIFIED CONNECTOR OR LIST THE FLORIDA PRODUCT |
| APPROVAL NUMBER NEXT TO THE SPECIFIED CONNECTOR. REPEAT |
| COMMENT. NOT ADDRESSED. |
| |
| 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ALL PRODUCT APPROVAL. SEC. 107.3.4.1 CITY AMENDMENTS. |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE REMOVE AND REPLACE ANY REVISED SHEET AND |
| SUBMIT OLD PLANS FOR REFERENCE. |
| |