2015-02-04 07:17:12 | 1) SHOW THE RELOCATED LAVATORY IN BATH #1 ON THE | | SANITARY RISER. WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | 2) AS DRAWN, THE SANITARY RISER DOES NOT MEET CODE. THE | | HORIZONTAL WET VENT HAS ONE TOO MANY LAVATORIES, ONE | | TOO MANY SHOWERS AND EXCEEDS THE MAXIMUM NUMBER OF | | FIXTURE UNITS FOR A 2" WET VENT PER TABLE P3108.3 OF | | THE 2010 FBCR SEC. P3108. | | 3) PLANS SHALL BEAR THE SEAL AND SIGNATURE OF THE | | DESIGN PROFESSIONAL PER THE FL. ADMIN. RULE 61G15 | | -23.002. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|