Plan Review Notes
Plan Review Notes For Permit 15020030
Permit Number 15020030
Review Stop P
Sequence Number 1
Notes
Date Text
2015-02-04 07:17:121) SHOW THE RELOCATED LAVATORY IN BATH #1 ON THE
 SANITARY RISER. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) AS DRAWN, THE SANITARY RISER DOES NOT MEET CODE. THE
 HORIZONTAL WET VENT HAS ONE TOO MANY LAVATORIES, ONE
 TOO MANY SHOWERS AND EXCEEDS THE MAXIMUM NUMBER OF
 FIXTURE UNITS FOR A 2" WET VENT PER TABLE P3108.3 OF
 THE 2010 FBCR SEC. P3108.
 3) PLANS SHALL BEAR THE SEAL AND SIGNATURE OF THE
 DESIGN PROFESSIONAL PER THE FL. ADMIN. RULE 61G15
 -23.002.
  