 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 SHOW THE LOCATION OF THE ELECTRICAL SERVICE AND
 DISCONNECT ON THE BUILDING. VERIFY THE MAIN DISCONNECT
 IS LOCATED AT THE POINT OF SERVICE. VERIFY THE
 UNPROTECTED SERVICE CONDUCTORS ARE NOT LOCATED IN THE
 BUILDING. INCLUDE A PANEL SCHEDULE FOR EACH PANEL. NEC
 230.70(A)(1)
  
 ADD RECEPTACLES (DINING, WALL AT STAIRS, KITCHEN,
 BEDROOM #3 AND #4) SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES 2 FEET OR
 MORE IN WIDTH HAVE A RECEPTACLE. NEC 210.52
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND
 REAR ELEVATIONS. NEC 210.8, 210.52(E)(1)
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED ON BALCONY. NEC
 210.8, 210.52(E)(3)
  
 SWITCH CONTROLLED LIGHTING OUTLETS ARE REQUIRED AT ALL
 ENTRANCES. NEC 210.70 (A) (2) (B)
  
 THE SMOKE DETECTORS MUST BE INTERCONNECTED. FBC R313.2
  
  