Plan Review Notes
Plan Review Notes For Permit 15020022
Permit Number 15020022
Review Stop M
Sequence Number 1
Notes
Date Text
2015-03-02 08:44:00PASS PROVISO
 1) REFER TO SECTION 503.2.5.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE 2010
 2) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL ALARM
 606.4.1 SUPERVISION. FBC (M) 2010
 3) REFER TO SECTION 304.11 GUARDS. FOR EQUIPMENT
 LOCATED LESS THAN 10 FT FROM THE EDGE OF THE ROOF.
 FBC (M) 2010
 4) REFER TO SECTION 307.2.3.1 WATER LEVEL MONITORING
 DEVICE FBC (M) 2010
 5) REFER TO SECTION 603.5 NONMETALLIC DUCTS. DO NOT
 PAINT FIBERGLASS OR FLEX DUCT 2010 FBC (M)
  