Plan Review Notes For Permit 15020022 |
Permit Number |
15020022 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-02-10 16:36:06 | PERMIT # 15020022 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PROVISO: | | | | 1) UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | AMENDMENTS. | | | | 2) PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL | | INITIATE A GENERAL FIRE ALARM CONDITION. (REFERS TO | | FIRE ALARM NOTE ON SHEET A1.5) | | | | SUE ELLEN CALDERON | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 644-7326 | | | | | | |
|