 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 IT IS NOT CLEAR IF THE ELECTRICAL SERVICE IS REPLACING
 AN EXISTING SERVICE OR IF A NEW ELECTRICAL SERVICE IS
 BEING PROPOSED. VERIFY THIS BUILDING/TENANT HAS
 SUFFICIENT FIRE SEPARATION TO QUALIFY AS A SEPARATE
 BUILDING AND TO HAVE ITS OWN ELECTRICAL SERVICE OR
 PROVIDE JUSTIFICATION FOR THE SERVICE PROPOSED. NEC
 230.2, 215.5, 230.71
  
 INDICATE THE REQUIRED FAULT CURRENT RATING FOR THE
 ELECTRICAL SERVICE AND PANELBOARDS. NEC 110.9, 110.10,
  
 ON THE ELECTRICAL PLAN PROVIDE A SAFETY LABELING
 SCHEDULE FOR FLASH PROTECTION FOR THE SERVICE, PANEL
 BOARDS AND MAIN DISCONNECTING MEANS. NEC 110.22
  
 PROVIDE A PERMANENT IDENTIFICATION PLAQUE WHICH SHOWS
 THE LOCATION OF THE ELECTRICAL SERVICES AND MAIN
 DISCONNECTS FOR THIS MULTIPLE OCCUPANCY BUILDING. NEC
 230.2 (E)
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 PROVIDE A NOTE ON PLANS REGARDING THE LIMITATIONS OF
 USE FOR MULTI-WIRE BRANCH CIRCUITS. NEC 210.4, 605.8(D)
  
 PROVIDE A NOTE ON PLANS REGARDING THE VOLTAGE
 LIMITATIONS AND VOLTAGE SEPARATION WITH BARRIERS
 REQUIRED FOR SWITCHES AND ADJACENT DEVICES. NEC 404.8
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY, VOICE AND DATA SYSTEMS.
  