Plan Review Notes
Plan Review Notes For Permit 15020017
Permit Number 15020017
Review Stop B
Sequence Number 1
Notes
Date Text
2015-02-13 15:44:02BUILDING PLAN REVIEW
 PERMIT: 15020017
 ADD: 550 S. ROSEMARY AVE. # 236
 CONT:M. SCIGIANO CONSTRUCTION
 TEL: (561)719-2496
  
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 2, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: FRI. FEB. 13/ 2015
 ACTION: DENIED
  
 1) THE DESIGNER OF RECORD HAS NOT INDICATED ON THE
 COVERSHEET, 2.1 SCOPE OF WORK NOR 4.1 EGRESS PLAN
 COMPLIANCE WITH THE 2010 FBC-EXIST. BLDG. CODE 101.5
 COMPLIANCE METHODS.
  
 2) MISSING INFORMATION FOR MINIMUM PLAN REVIEW. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.1 BUILDING
  
 2.1) OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
  
 2.2) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
  
 2.3) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC
 FIRE SPRINKLERS
  
 2.4) SHEET 4.1 THE LIFE SAFETY SHEET IS MISSING:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS THE BACK OF HOUSE EXIT IS NOT SHOWN ON PAGE
 4.1 BY THE RESTROOMS NOR DOES IT SHOW BY THE ELEVATOR
 THE EXIT, AND DISCHARGE.
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
  
 3) SHEET THE DEMOLITION PLAN 1.1 SHOWS AN EXISTING
 INDOOR/ OUTDOOR BAR. THE DOORS INTHIS AREA ARE BIFOLD
 DOORS ACORDIAN STYLE TO ONE SIDE ONLY, SHEET 2.1 SHOWS
 THE NORTH DOORS ACCORDIAN STYLE TO ONE SIDE WHERE THE
 EAST DOORS NOW SHOW ACCORDIAN STYLE DOORS ON BOTH SIDES
 OF THE OPENING/
 IS THIS A NEW DOOR CONFIGURATION THAT WILL REQUIRE
 PRODUCT APPROVALS FOR THE OPENING AND THE DESIGNER OF
 RECORD APPROVAL AS WELL.
  
 107.2.4 EXTERIOR WALL ENVELOPE. CONSTRUCTION DOCUMENTS
 FOR ALL BUILDINGS SHALL DESCRIBE THE EXTERIOR WALL
 ENVELOPE IN SUFFICIENT DETAIL TO DETERMINE COMPLIANCE
 WITH THIS CODE.
  
 107.2.4 EXTERIOR WALL ENVELOPE. CONSTRUCTION DOCUMENTS
 FOR ALL BUILDINGS SHALL DESCRIBE THE EXTERIOR WALL
 ENVELOPE IN SUFFICIENT DETAIL TO DETERMINE COMPLIANCE
 WITH THIS CODE. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL BE RESPONSIBLE FOR REVIEWING
 AND COORDINATING SUBMITTAL DOCUMENTS PREPARED BY
 OTHERS, INCLUDING PHASED AND DEFERRED SUBMITTAL ITEMS,
 FOR COMPATIBILITY WITH THE DESIGN OF THE BUILDING.
 THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4A) SHEET 3.1 AND 4.1 BOTH SHOW THE ELEVATOR SHAFT AND
 AN AREA TO THE RIGHT OF THE ELEVATOR 12 X 14 FT. THIS
 AREA DOES NOT SHOW ANY TYPE OF USAGE, NOTE FROM THE
 FURRTHEST CORNER IN THIS AREA SEE FBC-B 1017.4.3 TABLE
 AND SEATING AISLE ACCESSWAY LENGTH. THE LENGTH OF
 TRAVEL ALONG THE AISLE ACCESSWAY SHALL NOT EXCEED 30
 FEET (9144 MM) FROM ANY SEAT TO THE POINT WHERE A
 PERSON HAS A CHOICE OF TWO OR MORE PATHS OF EGRESS
 TRAVEL TO SEPARATE EXITS.
  
 4B) THE 2ND AREA OF CONCERN IS THE OUTDOOR SEATING AREA
 EAST OF THE MAIN ENTRY, THE NEW PROPOSED BAR HAS A
 LARGER FOOTPRINT & OCCUPANT LOAD, THE ACTUAL OUTDOOR
 SEATING AREA EXIT DISCHARGES IS NOT SHOWN NOR THE
 OCCUPANT LOAD OR EXITING PAST THE NORTH SIDE OF THE
 BAR., COMPLIANCE WITH FBC-B 1017.4.3 APPEARS TO BE A
 PROBLEM.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  