Plan Review Notes
Plan Review Notes For Permit 15020011
Permit Number 15020011
Review Stop E
Sequence Number 1
Notes
Date Text
2015-02-09 10:58:502/9/2015
 PROJECT: SUITE 302
 PERMIT#: 14120084, REVISION #15020011
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 PROVIDE CORRECTIONS TO THE ELECTRICAL PLANS TO COMPLY
 WITH REVIEW COMMENTS BELOW:
  
 1) NEC 215.2(A) (1) AND (2)
 REVISE THE RISER DIAGRAM TO INDICATE A FULL SIZED
 FEEDER TO PANEL MDP CAPABLE OF CARRYING THE TOTAL
 CONNECTED LOAD AND PROTECTED BY THE 600AMP OCPD IN
 PANEL MDP.
  
 2) NEC 215.2(A) (1)
 PROVIDE A LOAD CALCULATION TO INDICATE THE EXISTING MDP
 PANEL CAN SUPPORT THE ADDITIONAL LOAD OF THE NEW PANEL
 LP3B.
  
 3) NEC110.15, AND 408.3(F)
 REVISE THE PANEL SCHEDULE FOR PANEL LP3B TO FEED PANEL
 LP3 FROM PHASE A AND PHASE C. RIGHT NOW ONE PHASE
 FEEDING PANEL LP3 IS PHASE B (THE HIGH LEG) SEVERAL OF
 THE LOADS BEING FED IN PANEL LP3 ARE 120V LOADS AND
 SEVERAL OF THEM ARE CURENTLY INDICATED TO BE FED FROM A
 HIGH LEG.
  
 4) NEC110.15, AND 408.3(F)
 REVISE PANEL SCHEDULE FOR PANEL LP3B TO FEED PANEL LP3S
 FROM PHASE A AND PHASE C. RIGHT NOW ONE PHASE FEEDING
 PANEL LP3S IS PHASE B (THE HIGH LEG) THE LOADS BEING
 FED IN PANEL LP3S ARE ALL 120V LOADS AND 1/2 OF THEM
 ARE CURENTLY INDICATED TO BE FED FROM A HIGH LEG.
  
 5) WPB AMENDMENTS TO FBC 107.2
 INDICATE ALL WIRE SIZES IN ALL PANEL SCHEDULES.
  
 6) NEC 110.16 ARC FLASH PROTECTION.
 PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
  
 7) NEC 110.9
 VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A
 FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL
 CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  