Plan Review Notes For Permit 15020001 |
Permit Number |
15020001 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-03-12 18:18:25 | PLAN REVIEW COMMENTS | | | | 2ND REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE NOA THAT WAS SUBMITTED FOR THE SINGLE HUNG | | WINDOWS (NOA NO. 12-0127.16) WAS SUPERSEDED BY NOA NO. | | 14-0908.10 ON NOVEMBER 06, 2014. SUBMIT TWO COPIES OF | | THE CURRENT PRODUCT APPROVAL. | | | | 2) THE NOA THAT WAS SUBMITTED FOR THE STRUCTURAL | | MULLIONS (NOA NO. 12-0127.07) WAS SUPERSEDED BY NOA NO. | | 14-0908.08 ON NOVEMBER 06, 2014. THE INSTALLATION | | INSTRUCTION SHEETS WERE NOT SHRUNK TO FIT ON THE 8.5" X | | 11" PAPER AND SOME OF THE INFORMATION IS MISSING. MARK | | THE SIZES AND PRESSURES ON THE PRODUCT APPROVAL FOR THE | | MULLIONS THAT WILL BE USED. FBC 107.3.4 & DCA RULE 9N-3 | | | | 3) SPECIFY THE DESIGN PRESSURE AND THE GLASS TYPE FOR | | THE WINDOWS BY MARKING THEM ON THE PRODUCT APPROVALS. | | FBC 107.3.4 | | | | | | | | |
|