Plan Review Notes For Permit 15011106 |
Permit Number |
15011106 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-02-02 09:48:04 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. TYPES OF WINDOWS PROPOSED ARE NOT CLEAR. DOUBLE HUNG | | AND HORIZONTAL ROLLER WINDOW PRODUCT APPROVALS WERE | | SUBMITTED. THE WINDOW SCHEDULE HAS A NAMING CONVENTION | | OF "DHIM" AND "DHBI" (SEE BELOW). REVISE PLANS TO | | CLEARLY CORRELATE PRODUCT APPROVALS SUBMITTED WITH THE | | WINDOWS ON THE PLAN. | | | | FOR EXAMPLE - ONE WINDOWS IS "PGT 9700 DHBI" BUT THE | | PGT WINDOW PRODUCT APPROVAL IS A HORIZONTAL ROLLER | | MODEL 510. THE OTHER WINDOWS ARE "AC86 DHIM" BUT THE | | DOUBLE HUNG PRODUCT APPROVAL IS "WEATHER STOPPER 9500". | | |
|