Plan Review Notes For Permit 15011096 |
Permit Number |
15011096 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-02-02 13:03:34 | RESIDENTIAL (R3) REVISION MECHANICAL REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1-PLANS NEED TO BE SIGNED AND SEALED BY THE ARCHITECT | | OF RECORD AS REQUIRED BY SEC. 481 FLORIDA STATUTES. | | | | 2- SPECIFY THE SIZE OF THE TRANSFER GRILLS FOR BEDROOM | | #1 AND BEDROOM #2 TO SHOW COMPLIANCE WITH THE BALANCED | | RETURN AIR EXCEPTION #2 OF SEC.M1602.4 OF 2010 | | FBC-RESIDENTIAL. | | | | 3- SIZE OF MASTER BEDROOM TRANSFER DUCT DOESN'T COMPLY | | WITH THE BALANCED RETURN AIR EXCEPTION #1 OF SEC. | | M1602.4 OF 2010 FBC-RESIDENTIAL. DUCT NEEDS TO BE | | INCREASED 1-1/2 TIMES THE CROSS SECTIONAL AREA OF THE | | SUPPLY DUCT ENTERING THE ROOM AND THE DOOR NEEDS TO | | HAVE AT LEAST 1" UNDERCUT. | | NOTE: ALL THE SUPPLY AIR INTO THE MASTER SUITE SHALL BE | | INCLUDED WHEN SIZING THE TRANSFER DUCT. SEE EXCEPTION | | #3 OF SEC. M1602.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|