2015-02-02 13:03:34RESIDENTIAL (R3) REVISION MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1-PLANS NEED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OF RECORD AS REQUIRED BY SEC. 481 FLORIDA STATUTES.
  
 2- SPECIFY THE SIZE OF THE TRANSFER GRILLS FOR BEDROOM
 #1 AND BEDROOM #2 TO SHOW COMPLIANCE WITH THE BALANCED
 RETURN AIR EXCEPTION #2 OF SEC.M1602.4 OF 2010
 FBC-RESIDENTIAL.
  
 3- SIZE OF MASTER BEDROOM TRANSFER DUCT DOESN'T COMPLY
 WITH THE BALANCED RETURN AIR EXCEPTION #1 OF SEC.
 M1602.4 OF 2010 FBC-RESIDENTIAL. DUCT NEEDS TO BE
 INCREASED 1-1/2 TIMES THE CROSS SECTIONAL AREA OF THE
 SUPPLY DUCT ENTERING THE ROOM AND THE DOOR NEEDS TO
 HAVE AT LEAST 1" UNDERCUT.
 NOTE: ALL THE SUPPLY AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED WHEN SIZING THE TRANSFER DUCT. SEE EXCEPTION
 #3 OF SEC. M1602.4.
  