2015-05-04 12:50:38 | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND MECHANICAL | | REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY | | SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. | | | | 2- SHEET M-1: | | A) SPECIFY THE EQUIPMENT MANUFACTURER AND MODEL NUMBER | | FROM THE EQUIPMENT SIZING CALCULATIONS REQUIRED BY | | 403.6 OF 2010 FBC-ENERGY CONSERVATION. CAN NOT VERIFY | | WITHOUT THE EQUIPMENT SIZING CALCULATIONS LISTING THE | | EQUIPMENT. | | | | B) MASTER BEDROOM TRANSFER GRILL SPECIFIED DOESN'T | | COMPLY WITH SEC. M1602.4 OF 2010 FBC-RESIDENTIAL. ALL | | THE SUPPLY AIR INTO THE MASTER SUITE (INCLUDING | | BATHROOM AND CLOSET) NEED TO BE CONSIDERED WHEN SIZING | | THE TRANSFER GRILL. | | NOTES: | | (1)THERE ARE TWO 10" SUPPLY DUCTS ENTERING THE MASTER | | BEDROOM AND THE MASTER BATHROOM. 14" DUCT SPECIFIED ON | | PLANS DOESN'T COMPLY. REVISE AS REQUIRED. | | (2) RETURN AIR CAN NOT BE TAKEN FROM THE MASTER | | BATHROOM. SEC. M1602.2 OF 2010 FBC-RESIDENTIAL. REVISE | | AS REQUIRED. | | (3) REVISE SIZE OF SUPPLY GRILLS. FOR EXAMPLE 8" DUCT | | DOESN'T FIT ON 14X6 GRILL. REVISE AS REQUIRED. SEC. | | 107.2.1 CITY AMENDMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 |
|